5.3.4Install the Power Distribution Box on 8000 and 10,000VA Models

1.With the cover or distribution box removed, press the UPS and distribution box connectors together. Ensure that the connectors are fully seated.

2.Align the screw holes and press the power distribution box onto the UPS, making sure that the tabs at the bottom of the box fit into the slots on the UPS.

3.Attach the box to the UPS by installing screws into the two holes at the top of the box.

4.Tighten the screws.

5.Turn the output and input breakers On.

6.Start the UPS according to startup instructions.

7.Verify that the UPS lamp is illuminated.

5.3.5Distribution Box Electrical Connections

Electrical connections are made through a removable power distribution box that attaches to the rear of the UPS.

PD2-HDWR, PD2-HDWR-MBS, PD2-001, PD2-002, PD2-003, PD2-004, PD2-005 and PD2-006 models fit the 5000 and 6000VA models of the Liebert® GXT3

PD2-L630 fits the GXT3-6000RTL630

PD2-101, PD2-102, PD2-103, PD2-104, PD2-105 and PD2-106 models fit the 8000 and 10,000VA models of the Liebert GXT3

The installer must provide an upstream branch circuit breaker. The input circuit breaker on the dis- tribution box and the output circuit breaker on the rear of the power distribution box disconnect all power between the main cabinet and the distribution box.

Models equipped with a manual bypass breaker pass bypass power directly to the bypass breaker from the input terminal block. The input circuit breaker on the distribution box does not disconnect power from the manual bypass breaker.

Table 1 Branch circuit breaker ratings

Unit Rating Maximum Breaker Rating

5000VA

6000VA

8000VA

D Type 30A Long Delay

D Type 60A Long Delay

10,000VA

Figure 15 Distribution box electrical connections diagram

UPS

Input

Output

CB

CB

Maintenance

Bypass Breaker

Input Output

Indicator Indicator

Utility Input

Output

Distribution

POD

 

 

 

 

 

UPS

 

 

 

 

 

 

Input

 

 

 

 

 

Output

 

Output

 

 

 

 

 

 

 

 

 

 

 

 

 

CB

 

 

 

 

 

CB

 

 

 

 

Maintenance

 

 

 

 

Terminal

 

 

Bypass Breaker

 

 

 

 

Block

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Optional

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Output

 

 

 

Input

Output

 

 

Distribution

 

 

 

 

 

Plate

 

 

Indicator

Indicator

 

 

 

 

 

 

 

Utility Input

External

Branch CB Distribution Box Electrical Connections

for 5000 and 6000VA Models

External

Branch CB Distribution Box Electrical Connections for 8000 and 10,000VA Models

19

Page 25
Image 25
Emerson GXT3-6000RT208 user manual Distribution Box Electrical Connections, Branch circuit breaker ratings