Troubleshooting

11.0TROUBLESHOOTING

This section indicates various UPS symptoms a user may encounter and provides a troubleshooting guide in the event the UPS develops a problem. Use the following information to determine whether external factors caused the problem and how to remedy the situation.

11.1UPS Symptoms

The following symptoms indicate the Liebert® GXT3is malfunctioning:

The relative indicators illuminate, indicating the UPS has detected a problem.

An alarm buzzer sounds, alerting the user that the UPS requires attention.

11.1.1Indicators

In addition to the fault indicator being illuminated, one or more of LED segments of battery level indi- cator will also be illuminated to provide a diagnostic aid to the user, as shown in Figure 26. The descriptions are listed in Table 4.

Figure 26 Battery level indicator

 

 

 

 

 

 

 

 

 

 

 

 

A

B

C

D

E

 

Table 4

Indicator descriptions

 

 

 

 

 

 

 

 

 

 

 

 

 

Indicator

 

 

Diagnosis/Audible alarm

 

 

 

 

 

 

 

 

 

 

A - E

 

On bypass from output overload (half-second beep every half-second)

 

 

 

 

 

 

A

 

On bypass due to overtemperature condition (1-second beep every 4 seconds)

 

 

 

 

 

 

B

 

On bypass due to DC bus overvoltage (1-second beep every 4 seconds)

 

 

 

 

 

 

C

 

On bypass due to DC/DC power supply failure (1-second beep every 4 seconds)

 

 

 

 

 

 

 

D

 

PFC failure (1-second beep every 4 seconds)

 

 

 

 

 

 

 

 

 

E

 

On bypass due to inverter failure (1-second beep every 4 seconds)

 

 

 

 

 

 

A&B

 

UPS Failure (includes dual-fan failure, single-fan failure under certain conditions and battery

 

charger failure) and continuous alarm

 

 

 

 

 

 

 

 

A&C

 

UPS failed battery test (2-second beep every 60 seconds)

 

 

 

 

 

 

 

A&D

 

Maintance bypass switch on (continuous)

 

 

 

 

 

 

 

 

 

A&E

 

Bypass feedback (1-second beep every 4 seconds)

 

 

 

 

 

 

 

 

B&C

 

REPO (one quarter-second beep at quarter-second intervals)

 

 

 

 

 

 

 

 

 

B&E

 

Short circuit on the output

 

 

 

 

 

 

 

 

 

 

 

C&E

 

UPS shutdown by command from communication (USB port or Liebert® IntelliSlot® port) (no

 

audible)

 

 

 

 

 

 

 

 

 

 

 

 

Utility LED flash

L-N reverse

 

 

 

 

 

 

 

 

 

 

Battery Indicator

Internal battery source not available (continuous horn); check battery connection, power down

Flashing

and reboot UPS

 

 

 

 

 

Bypass Indicator

Utility power voltage or frequency is out of tolerance; bypass is unavailable

Flashing

 

 

 

 

 

 

 

A - E indicators are shown in Figure 26

 

 

 

 

 

35

Page 41
Image 41
Emerson GXT3-6000RT208 user manual UPS Symptoms, Troubleshooting, Indicators, Indicator Diagnosis/Audible alarm