Installation and Configuration

Terminal Block Connections

Conduit entry holes are provided on the rear and side of the box. Input and output wiring should not share the same conduit. Emerson recommends using strain relief when installing the wire.

Table 2

Electrical specifications

 

 

 

 

 

 

 

 

 

 

 

Recommended

Recommended Wire

Maximum Wire

Terminal

 

 

(Maximum) External

(Including ground wire)

Accepted by

Tightening

UPS Model

Overcurrent Protection

(75°C copper wire)

Terminal Block

Torque

GXT3-5000RT208

 

10AWG (4mm2)

8AWG (6mm2)

 

GXT3-6000RT208

30A

20 in-lb

GXT3-6000RTL630

 

 

 

 

 

 

 

 

(2.26 Nm)

GXT3-8000RT208

 

2

2

 

 

GXT3-10000RT208

60A

6AWG (10mm )

4AWG (16mm )

 

Figure 16 Terminal block connections

Liebert GXT3-5000 and 6000RT208

 

 

 

 

 

 

 

 

L2

N

L1

 

L2

N

L1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OUTPUT

 

 

 

 

 

 

 

 

 

INPUT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Liebert GXT3-8000 and 10,000RT208

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

L2

N

L1

 

 

 

 

 

 

 

 

L2

N

 

L1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OUTPUT

 

 

 

 

 

 

 

 

 

INPUT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NOTE

1. Emerson recommends installing a UL489-approved breaker upstream of unit.

2.The installer must provide circuit breaker protection according to local codes. The utility disconnect should be within sight of the UPS or have appropriate an appropriate lock-out. Maintain service space around the UPS or use flexible conduit.

3.The installer must provide output distribution panels, circuit breaker protection or emergency disconnects according to local codes. Output circuits must not share a common conduit with any other wiring.