Emerson GXT3-6000RT208 user manual Manual Battery Test, Put the Liebert GXT3 in Manual Bypass

Models: GXT3-6000RT208

1 52
Download 52 pages 4.18 Kb
Page 33
Image 33

Operation

8.3Manual Battery Test

To initiate a manual battery test, press the On/Alarm Silence/Manual Battery Test button for at least half a second while the UPS is operating from utility power with no alarm conditions present.

If only the first two of the five LED segments illuminate, allow the UPS to recharge the batteries for 24 hours.

Retest the batteries after 24 hours of charging.

After the batteries have been retested, if only two of the five Battery LEDs illuminate, contact your local Emerson representative or Emerson Network Power Channel Support.

If none of the five Battery LEDs illuminate during a manual battery test, check the battery con- nection and allow the UPS to recharge the batteries for 1 hour, then initiate a manual battery test again.

If none of the five Battery LEDs illuminate during the second manual battery test, replace batter- ies and contact your local Emerson representative or Emerson Channel Support.

8.4Put the Liebert® GXT3in Manual Bypass

Press the Standby/Manual Bypass button and hold it for about 2 seconds while the UPS is in Utility (AC) Mode. The UPS will transfer the connected loads to the internal bypass. If the internal bypass is not available because of utility power problems, pressing this button once will be ignored. Bypass operation is indicated by an audible alarm and illuminated amber Bypass indicator. (If other indica- tors are illuminated, refer to 11.0 - Troubleshooting.)

8.5Shut Down the Liebert GXT3

1.Transfer the UPS to manual bypass by pressing the Standby/Manual Bypass button and holding it for about 2 seconds.

If manual bypass is not available, disregard the first step.

2.Press the Standby/Manual Bypass button twice within four seconds, each time holding it for about two seconds.

Power to the connected loads is now Off.

8.6Disconnecting Input Power from the Liebert GXT3

1.After the UPS has been shut down as detailed in 8.5 - Shut Down the Liebert GXT3, turn off the Output Circuit Breaker.

2.Wait 30 seconds and verify that all indicators have turned Off and the fan has stopped; this indicates that the power-off is complete.

3.Turn the external battery cabinet breaker switch to the Off position if the UPS has an external battery cabinet.

After powering off the UPS, the UPS ceases output and the load is powered Off.

8.7Maintenance Bypass

Maintenance Bypass Mode is used when maintenance or replacement is required. To place the unit in Maintenance Bypass:

1.Place the UPS on internal bypass. This may be done by either of the following methods:

a.Press the Off button on the front panel one time.

b.Slide the bracket away from the manual bypass breaker on the rear of the UPS. This requires loosening the captive screw and sliding the bracket up and away from the Manual Bypass breaker.

2.Move the Manual Bypass breaker on the rear of the UPS to the bypass position. This requires loosening the captive screw and sliding the bracket up and away from the Manual Bypass breaker.

27

Page 33
Image 33
Emerson GXT3-6000RT208 user manual Manual Battery Test, Put the Liebert GXT3 in Manual Bypass, Shut Down the Liebert GXT3