2.5 Intrinsically safe installation

Control units type MEP3* and head amplifier units to type MEP3** and ***S*P*H** are approved by ATEX as intrinsically safe equipment to II 1 G Ex ia IIC. Refer to safety instruction IP221/SI and local code of practice.

The following points must be noted when installing these units:-

i)The cable from the head amplifier to the control unit must be screened, and the screen must be connected at the control unit end only.

ii)On I.S systems the cable from sensor to head amplifier must be less than 15 meters long. If more than 3 meter is required, special cable must be used.

iii)The control unit must be earthed using at least 4mm2 wire. All screen earth and main earth connections must be commoned. In the case of the rack unit, MEP3B, the chassis must be earthed and each unit connected independently to the chassis earth.

iv)I.S. cables must exit the control separately from the mains and relay cables.

v)It is the responsibility of the installer to ensure that local codes of practice are followed. Intrinsically Safe Electropulse is approved by ATEX & standards EN50014 and EN50020.

The certificates are listed below:

Description

Approval

To Standard

Certificates of Conformity

Code

 

MEP3 L

II (1) G [EExia] IIC

EN 50014 & EN 50020

MEP3 R/MEP3 B

 

 

Sensor & Head Amplifier

II 1 G EExia IIC T4

EN 50014 & EN 50020

Adjacent Amplifier

II 1 G EExia IIC T4

EN 50014 & EN 50020

Sensors (separate)

II 1 G EExia IIC T4

EN 50014 & EN 50020

 

 

 

Table 2.2 - Approvals

15

Page 15
Image 15
Emerson IP221 appendix Intrinsically safe installation, Certificates of Conformity, II 1 G EExia IIC EN 50014 & EN