Instruction Manual
Model NGA2000 HFID
All new external gas tubing (except for PURGE IN/OUT and SAMPLE BYPASS) is strongly recommended, preferably pre- cleaned, stainless steel, gas chromatograph
Gas line connections are compression fit- tings. Do not use pipe thread tape.
Since the oxidation of hydrogen is accompanied by the formation of water vapor, the Exhaust tubing always should be slanted downward at least 6 degrees from horizon-
tal. Otherwise, water may accumulate in the line, causing back pressure and noisy readings, or may back up in the line and flood the burner. Depending on the percent of water vapor in the sam- ple, the sample bypass out connection may have condensation. Proper drainage may be required.
If the sample is toxic or noxious, or is to be reclaimed, connect the Bypass outlet to a suitable disposal system. Do not use any device that may cause back pressure in the line.
Purge air and burner air should be supplied from separate sources.
! WARNING
PURGE | BURNER |
AIR OUT | AIR IN |
Possible electric shock, explosion or toxic gas hazard. See front of module
| FUEL |
BURNER | IN |
EXHAUST | MAXIMUM |
OUT | INPUT |
VENT TO SAFE AREA | PRESSURE |
SLOPE DOWNWARD 6! | FUEL: 50 psig(3445 hPa) |
MINIMUM | BURNER AIR: 50 psig (3445 hPa) |
WARNING | SAMPLE: 8 psig (551 hPa) |
PURGE AIR: 20 psig (1378 hPa) | |
HOT ! | REG AIR: 25 psig (1722 hPa) |
REGULATE | PURGE | ATTENTION | PRESSURE |
CHAUD ! | |||
D | AIR IN |
| RELIEF |
| VALVE | ||
|
|
| |
|
|
| HEATED |
|
|
| SAMPLE IN |
HEATED
SAMPLE
BYPASS OUT
!ATTENTION Danger d'electrocution, d'explosion ou d'emanation de gaz toxique. Se refere aux details inscrits surla face du module.
Figure
Installation | Rosemount Analytical Inc. A Division of Emerson Process Management |