Empire Comfort Systems DVD36FP3, DVD42FP5 Termination Clearances, Vertical Sidewall Installations

Models: DVD48FP5 DVD36FP3 DVD42FP5 DVD32FP3-1, DVD36FP3-1, DVD42FP3-1, DVD48FP3-1,DVD32FP5-2, DVD36FP5-2, DVD42FP5-2, DVD48FP5-2 DVD48FP3 DVD42FP3

1 52
Download 52 pages 60.93 Kb
Page 21
Image 21
TERMINATION CLEARANCES
Figure 34

TERMINATION CLEARANCES

Termination clearance for buildings with combustible and noncombustible exteriors.

Vertical Sidewall Installations

Important! Minimum clearance between vent pipes and combustible materials is three (3") (76mm) on top, and (1") (25mm) on bottom and sides.

Important! When vent termination exits through foundation less than 20" below siding outcrop, the vent pipe must flush up with the siding. SD-985 termination cap must be used.

Information on Various Venting Routes and Components

Important: It is always best to locate the fireplace in such a way that minimizes the number of offsets and horizontal vent length.

Since it is very important that the venting system maintain its balance between the combustion air intake and the flue gas exhaust, certain limitations as to vent configurations apply and must be strictly adhered to.

The graph showing the relationship between vertical and horizontal side wall venting will help to determine the various vent lengths allowable.

The horizontal vent run refers to the total length of vent pipe from the flue collar of the fireplace to the face of the outer wall. The maximum horizontal vent run is 20 feet (457 cm) when the vertical vent rise is 8 feet (244 cm) (See Figure 19). Venting terminals shall not be recessed into wall or siding.