Specifications

CLEARANCES TO COMBUSTIBLES - 1200 INSERT:

Table 3: 1200 Insert Clearance to Combustibles.

A

Minimum clearance to an unshielded side wall

10” (254 mm)

����

 

 

B

Minimum clearance to an unshielded 8” (203 mm) mantle

21” (533 mm)

 

 

 

C

Minimum top facing (protruding 3⁄4” [19 mm]) clearance

171⁄2” (445 mm)

��������

E

† From front of door opening to edge of floor protection

USA 16” (406 mm)

 

D

Minimum side facing (protruding 3⁄4” [19 mm]) clearance

1” (25 mm)

 

 

 

 

CND 18” (450 mm)

 

 

 

F

† From side/back of unit to edge of floor protection

USA 6” (152 mm)

 

 

 

 

CND 8” (200 mm)

 

 

 

 

 

FLOOR PROTECTION:

If unit is raised 0” - 2” (0mm-51mm); 1” (25mm) non-combustible material with k value = 0.84 or equivalent.

If unit is raised 2” - 8” (51mm-203mm); 1⁄2” (13mm) non-combustible material with k value = 0.84 or equivalent. If unit is raised greater than 8” (203 mm) or more; any non-combustible material can be used.

Table 4: 1200 Insert Minimum Fireplace Size.

 

Masonry

Zero Clearance

 

 

 

Minimum Depth

131⁄2” (343mm)

14” (279mm)

 

 

 

Minimum Width at back of fireplace

223⁄8” (568mm)

23” (584mm)

 

 

 

Minimum Width at front of fireplace

27” (686mm)

271⁄4” (692mm)

 

 

 

Minimum Width at front of fireplace to include shroud

333⁄4” (857mm)

34” (864mm)

 

 

 

Minimum Height

191⁄4” (489mm)

20” (508mm)

 

 

 

CLEARANCES TO COMBUSTIBLES - 1700 INSERT:

Table 5: 1700 Insert Clearance to Combustibles.

A

Minimum clearance to an unshielded side wall

10”

(254 mm)

 

 

 

 

B

Minimum clearance to an unshielded 8” (203 mm) mantle

24”

(610 mm)

 

 

 

C

Minimum top facing (protruding 3⁄4” [19 mm]) clearance

191⁄2” (495 mm)

 

 

 

 

D

Minimum side facing (protruding 3⁄4” [19 mm]) clearance

1”

(25 mm)

 

 

 

E

† From front of door opening to edge of floor protection

USA 16” (406 mm)

 

 

CND 18” (450 mm)

 

 

 

F

† From side of unit to edge of floor protection

USA 6” (152 mm)

 

 

CND 8” (200 mm)

 

 

 

 

����

��������

 

 

 

 

 

FLOOR PROTECTION:

If unit is raised 0” - 2” (0mm-51mm); 1” (25mm) non-combustible material with k value = 0.84 or equivalent.

If unit is raised 2” - 8” (51mm-203mm); 1⁄2” (13mm) non-combustible material with k value = 0.84 or equivalent. If unit is raised greater than 8” (203 mm) or more; any non-combustible material can be used.

Table 6: 1700 Insert Minimum Fireplace Size.

 

Masonry

Zero Clearance

 

 

 

Minimum Depth

18” (457mm)

181⁄2” (470mm)

 

 

 

Minimum Width at back of fireplace

223⁄8” (568mm)

23” (584mm)

 

 

 

Minimum Width at front of fireplace

27” (686mm)

271⁄4” (692mm)

 

 

 

Minimum Width at front of fireplace to include shroud

333⁄4” (857mm)

34” (864mm)

 

 

 

Minimum Height

191⁄4” (489mm)

20” (508mm)

 

 

 

13

Page 13
Image 13
Enviro 1700 Fireplace Freestanding, C-11116, 1700 Insert † From front of door opening to edge of floor protection