Installation
MASONRY CHIMNEY INSTALLATION - FREESTANDING:
DO NOT CONNECT THIS UNIT TO A CHIMNEY FLUE SERVING ANOTHER APPLIANCE.
A
COMBUSTIBLES - 1200 FREESTANDING” or “CLEARANCES TO COMBUSTIBLES - 1700 FREESTANDING”. When venting into a
masonry chimney, the floor protector must be installed directly below the chimney vent and 2” (50.8 mm) on either side of the chimney vent.
Vent the stove into a clean, lined, approved masonry chimney in good condition, conforming to local building codes and meeting the minimum standards of the National Fire Protection Association (NFPA). Make sure there are no cracks, loose mortar or other signs of deterioration and blockage. Have the chimney cleaned before the stove is installed and operated, or vent with a listed 6” (150 mm) factory- built chimney suitable for use with solid fuels and conforming to
When connecting the stove through a combustible wall to a masonry chimney, additional steps are required. Consult the chimney connector manufacturer and
refer to Figure 28.
All chimneys in Canada must be fully lined with a 6" (150 mm) stainless steel liner from the chimney connector to the top of the chimney.
Chimney thimble; | |
or metal) and must be cemented in place. | |
| Single or listed double |
| wall chimney connector. |
| Woodstove |
Optional |
|
fan. |
|
| Pedestal |
| Hearth pad. |
Outside air connection | Floor. |
through wall or floor. |
|
Figure 27: Installation into a masonry chimney. | Figure 28: Installation into chimney through a |
| combustible wall. |
27