Envision Peripherals R-410A Pressure Drop, Single Speed Models, Dual Capacity Models

Models: R-410A

1 40
Download 40 pages 13.59 Kb
Page 37
Image 37
Pressure Drop

ENVISION RESIDENTIAL INSTALLATION MANUAL

Pressure Drop

Single Speed Models

Model

GPM

 

Pressure Drop (psi)

 

30°F

50°F

70°F

90°F

110°F

 

 

 

3.0

0.9

0.9

0.8

0.7

0.7

022

4.5

1.7

1.6

1.5

1.4

1.3

6.0

2.8

2.7

2.5

2.3

2.2

 

 

8.0

4.7

4.4

4.1

3.9

3.6

 

4.0

1.5

1.4

1.3

1.2

1.1

030

6.0

3.0

2.8

2.7

2.5

2.3

8.0

5.1

4.8

4.5

4.2

3.9

 

 

10.0

7.7

7.2

6.8

6.3

5.8

 

5.0

1.0

1.0

0.9

0.8

0.8

036

7.0

2.1

1.9

1.8

1.7

1.6

9.0

3.6

3.3

3.0

2.8

2.6

 

 

12.0

6.3

5.9

5.5

5.1

4.8

 

5.0

0.8

0.7

0.7

0.7

0.6

042

8.0

2.1

2.1

1.9

1.8

1.7

11.0

4.2

4.1

3.8

3.5

3.3

 

 

14.0

7.6

6.7

6.3

5.8

5.4

 

6.0

1.1

1.0

1.0

0.9

0.8

048

9.0

2.3

2.1

2.0

1.9

1.7

12.0

3.9

3.7

3.4

3.2

3.0

 

 

16.0

6.7

6.3

5.9

5.5

5.1

 

9.0

2.4

2.2

2.1

2.0

1.8

060

12.0

3.9

3.6

3.4

3.2

2.9

15.0

5.7

5.3

5.0

4.7

4.3

 

 

20.0

9.5

8.9

8.3

7.8

7.2

 

12.0

3.0

2.8

2.6

2.4

2.2

070

15.0

4.4

4.0

3.8

3.5

3.3

18.0

6.0

5.5

5.1

4.8

4.4

 

 

24.0

9.7

9.1

8.5

7.9

7.3

Dual Capacity Models

Model

GPM

 

Pressure Drop (psi)

 

30°F

50°F

70°F

90°F

110°F

 

 

 

4.0

1.4

1.3

1.2

1.1

1.0

026 full

6.0

2.8

2.6

2.4

2.3

2.1

 

 

 

 

 

 

load

8.0

4.7

4.4

4.1

3.8

3.5

 

10.0

7.0

6.6

6.2

5.8

5.3

 

3.0

0.8

0.7

0.7

0.7

0.6

026 part

5.0

2.0

1.8

1.7

1.6

1.5

 

 

 

 

 

 

load

7.0

3.6

3.4

3.2

3.0

2.8

 

9.0

5.8

5.5

5.1

4.8

4.4

 

5.0

1.2

1.2

1.1

1.0

1.0

038 full

7.0

2.2

2.1

1.9

1.8

1.7

 

 

 

 

 

 

load

9.0

3.4

3.2

3.0

2.8

2.6

 

11.0

4.9

4.6

4.3

4.0

3.7

 

4.0

0.9

0.8

0.8

0.7

0.7

038 part

6.0

1.7

1.6

1.5

1.4

1.3

 

 

 

 

 

 

load

8.0

2.8

2.6

2.5

2.3

2.1

 

10.0

4.2

3.9

3.7

3.4

3.2

 

6.0

1.2

1.2

1.1

1.0

1.0

049 full

9.0

2.4

2.2

2.1

2.0

1.8

 

 

 

 

 

 

load

12.0

3.9

3.6

3.4

3.2

2.9

 

15.0

5.7

5.3

5.0

4.7

4.3

 

5.0

0.9

0.9

0.8

0.8

0.7

049 part

8.0

2.0

1.8

1.7

1.6

1.5

 

 

 

 

 

 

load

11.0

3.4

3.1

2.9

2.8

2.5

 

14.0

5.0

4.7

4.4

4.1

3.8

 

8.0

1.8

1.7

1.6

1.4

1.3

064 full

12.0

3.8

3.5

3.3

3.0

2.8

 

 

 

 

 

 

load

16.0

6.5

6.0

5.6

5.2

4.8

 

20.0

9.7

9.1

8.5

8.0

7.4

 

6.0

1.0

0.9

0.9

0.8

0.8

064 part

10.0

2.6

2.5

2.3

2.1

2.0

load

14.0

5.0

4.7

4.4

4.1

3.8

 

18.0

8.1

7.6

7.1

6.6

6.1

 

12.0

3.2

3.0

2.8

2.6

2.4

072 full

15.0

4.5

4.2

4.0

3.7

3.4

 

 

 

 

 

 

load

18.0

6.0

5.7

5.3

4.9

4.6

 

21.0

7.8

7.3

6.8

6.4

5.9

 

10.0

2.3

2.1

2.0

1.9

1.7

072 part

13.0

3.6

3.3

3.0

2.8

2.6

load

16.0

5.0

4.6

4.3

4.0

3.7

 

19.0

6.5

6.2

5.8

5.4

5.0

37