Fixed or constant frequency

 

 

 

 

output mode: In normal mode

 

 

 

 

the UPS output frequency will

 

 

 

 

automatically be set to the

 

 

 

 

utility frequency and is

 

 

 

 

synchronized with that

 

 

 

 

frequency. When set to cf50Hz

 

 

 

 

mode, the UPS inverter output

 

 

 

 

frequency will always be 50Hz.

 

 

 

 

When set to cf60Hz mode, the

 

 

 

 

UPS inverter output frequency

 

 

 

 

will always be 60Hz.

 

 

 

 

Setting the UPS to a fixed or

 

 

 

 

constant output frequency

 

 

 

 

should be done when the input

 

 

 

 

source is a generator.

 

 

 

 

Depress the “Next Page”

 

 

 

 

 

 

 

 

 

 

 

 

button.

 

 

 

 

The next parameter displayed

 

 

 

 

shows the inverter output

 

 

 

 

voltage adjustment. The

 

 

 

 

adjustment can be set to 0%

 

 

 

 

(shown), +1%, -1%, +2%, -2%,

 

 

 

 

+3%or -3% (not shown).

 

 

 

 

Depress the “Next Page”

 

 

 

 

button.

X

 

 

The next parameter displayed

shows the UPS unit address. If only one UPS is being used, the address should be set to “d0” as shown.

If multiple parallel UPS units are connected in a parallel configuration of 6, 12, 18 or 24kVA, or 6, 12, 18kVA N+1 operation, the units would be addressed “d0”, “d1”, “d2” and “d3”. See the parallel mode configuration section on page 30 of this manual for more details.

Depress the “Next Page” button.

The next parameter displayed shows the UPS position when it is used in a parallel configuration. The positions are “01”, “02”, “03”, or “04”.

If only one UPS is being configured, the position should be set to “01” as shown.

26

Page 26
Image 26
Falcon FN4KRM-2TXI, FN6KRM-2TXI, FN3KRM-2TXI manual Fixed or constant frequency