UA88382 USB Interface Option Card
This option card supports the connection of (1) USB interface cable for use with UPSilon remote monitoring, management and unattended O/S shutdown software.
2 | 1 |
3 4
Pin 1 | - VCC (+5V) |
|
| CN1 | |
Pin 2 | - D- | Pin 1 | - REPO 1 | ||
| |||||
Pin 3 | - D+ | Pin 2 | - REPO2 | 1 2 | |
Pin 4 | - Ground |
|
|
|
UA88383 Dry Contact Interface Option Card
This card provides dry contact closure signals for UPS on bypass, utility normal, inverter on, low
battery, abnormal battery, UPS summary alarm. It also provides EPO and remote UPS shutdown capability.
1 2 3 4 5 6 7 8 9 10
USHA SNMP/HTTP Agent Option Card
Now you can monitor and manage your Falcon Electric FN Series UPS across an Ethernet LAN, WAN, Enterprise Network or via the World Wide Web. With our Universal SNMP/HTTP Agent board (USHA), remote management is easy using a standard web browser or Network Management Software (NMS).
Remote SNMP/HTTP UPS management is a simple matter of inserting our USHA board into the designated option port provided on the rear panel of every FN Series UPS.
The USHA board is supplied with a SNMP UPS MIB II compliant
Pin 1 - UPS on Bypass Pin 2 - Utility Abnormal Pin 3 - Utility Normal Pin 4 - Inverter On Pin 5 - Low Battery Pin 6 - Abnormal Battery
Pin 7 - UPS Summary Alarm Pin 8 - Common
Pin 9 - Shutdown UPS (+) signal Pin 10 - Shutdown UPS
Pins 9 & 10 apply
Remote server and computer shutdown client software is also provided on the CD that is shipped with this option. The software supports the shutdown of multiple servers or computers