UA88382 USB Interface Option Card

This option card supports the connection of (1) USB interface cable for use with UPSilon remote monitoring, management and unattended O/S shutdown software.

2

1

3 4

Pin 1

- VCC (+5V)

 

 

CN1

Pin 2

- D-

Pin 1

- REPO 1

 

Pin 3

- D+

Pin 2

- REPO2

1 2

Pin 4

- Ground

 

 

 

UA88383 Dry Contact Interface Option Card

This card provides dry contact closure signals for UPS on bypass, utility normal, inverter on, low

battery, abnormal battery, UPS summary alarm. It also provides EPO and remote UPS shutdown capability.

1 2 3 4 5 6 7 8 9 10

USHA SNMP/HTTP Agent Option Card

Now you can monitor and manage your Falcon Electric FN Series UPS across an Ethernet LAN, WAN, Enterprise Network or via the World Wide Web. With our Universal SNMP/HTTP Agent board (USHA), remote management is easy using a standard web browser or Network Management Software (NMS).

Remote SNMP/HTTP UPS management is a simple matter of inserting our USHA board into the designated option port provided on the rear panel of every FN Series UPS.

The USHA board is supplied with a SNMP UPS MIB II compliant "snap-in" Management Information Base (MIB). The MIB is compatible with HP OpenView and other Network Management Software (NMS).

Pin 1 - UPS on Bypass Pin 2 - Utility Abnormal Pin 3 - Utility Normal Pin 4 - Inverter On Pin 5 - Low Battery Pin 6 - Abnormal Battery

Pin 7 - UPS Summary Alarm Pin 8 - Common

Pin 9 - Shutdown UPS (+) signal Pin 10 - Shutdown UPS (-) signal

Pins 9 & 10 apply 6-25Vdc for 5 seconds to activate shutdown.

Remote server and computer shutdown client software is also provided on the CD that is shipped with this option. The software supports the shutdown of multiple servers or computers “in-band” across any Ethernet LAN. The client software may be installed on as many systems as required and supports most MS Windows and server platforms, in addition to

LINUX.

34

Page 34
Image 34
Falcon FN4KRM-2TXI, FN6KRM-2TXI, FN3KRM-2 UA88382 USB Interface Option Card, UA88383 Dry Contact Interface Option Card