4.0PRE-INSTALLATION DETAILS
Falcon Electric, Inc. is not responsible for shipping damage or for filing shipping damage claims. Visually inspect the equipment for freight damage. If any equipment has been damaged during shipment, retain the shipping pallet and packing materials for inspection by the carrier, and immediately file a claim for “shipping damage” with the carrier. If you discover damage after acceptance, file a claim for “concealed damage”.
To file a claim for shipping damage or concealed damage:
a.YOU MUST file with the carrier within 15 days of receipt of the equipment;
b.YOU MUST send a copy of the damage claim within 15 days to Falcon Electric, Inc.
WARNING
The UPS, Transformer and Battery Modules are very heavy. Use the proper lifting equipment and take the proper precautions when lifting or moving them.
1.Always install the FN system indoors in a controlled environment.
2. Install the FN modules in a location with unrestricted airflow around the front and rear sides of the modules, away from water, flammable liquids, gases, corrosive, and conductive contaminants.
3.Maintain a minimum clearance of 4 inches in the front and rear of the UPS.
4.Maintain an ambient temperature range of 32ºF to 104ºF (0ºC to 40ºC). To assure the maximum life of the batteries, operation in an ambient temperature of 68ºF to 77ºF (20ºC to 25ºC) is recommended.
OPERATION IN TEMPERATURES ABOVE 77ºF (25ºC) WILL REDUCE BATTERY LIFE.
5.The FN Series Rackmount system modules must be installed in a standard 19” equipment rack having hard mounted shelves under the modules to properly support their weight.
6.When selecting a suitable rack location for the UPS, Transformer and battery bank(s) always verify the floor loading capabilities:
4.1 Floor Loading Requirements
a. VERIFY THE FLOOR OR SUPPORTING SURFACE UNDER THE EQUIPMENT RACK IS RATED TO SUPPORT THE WEIGHT OF THE TOTAL WEIGHT OF THE RACK, THE FN MODULES AND ALL OTHER EQUIPMENT INSIDE THE RACK.
UPS Module:
(1)
(2)
(3)
(4)
Battery Bank Modules (for all FN Rackmount models)
(1)
(2)
(3)
(4)
Output Transformer Module (for all FN Rackmount models)
(1)
(2)
(3)
(4)