The next parameter displayed

 

 

 

 

shows the UPS unit address. If

 

X

 

 

only one UPS is being used, the

 

 

 

address should be set to “d0”

 

 

 

 

 

 

 

 

as shown.

 

 

 

 

If multiple parallel UPS units are

 

 

 

 

connected on a parallel configu-

 

 

 

 

ration of 6, 12, 18 or 24kVA, or 6,

 

 

 

 

12, 18kVA N+1 operation, the

 

 

 

 

units would be addressed “d0”,

 

 

 

 

“d1”, “d2” and “d3”. See the

 

 

 

 

parallel mode configuration sec-

 

 

 

 

tion of this manual for more

 

 

 

 

details.

 

 

 

 

To change between these

 

 

 

 

settings, depress the “Previous

 

 

 

 

Page/Change Setting” button.

 

 

 

 

Repeat pressing the button until

 

 

 

 

the desired address

 

 

 

 

setting is displayed. All setting

 

 

 

 

changes will be saved when

 

 

 

 

prompted at the end of the

 

 

 

 

parameter setup.

 

 

 

 

Depress the “Next Page” button.

 

 

 

 

The next parameter displayed

 

 

 

 

shows the UPS position when

 

 

 

 

used in a parallel configuration.

 

 

 

 

The positions are “01”, “02”,

 

 

 

 

“03”, or “04”.

 

 

 

 

If only one UPS is being

 

 

 

 

configured, the position should

 

 

 

 

be set to “01” as shown.

 

 

 

 

To change between these

 

 

 

 

settings, depress the “Previous

 

 

 

 

Page/Change Setting” button.

 

 

 

 

Repeat pressing the button until

 

 

 

 

the desired UPS position

 

 

 

 

setting is displayed. All setting

 

 

 

 

changes will be saved when

 

 

 

 

prompted at the end of the

 

 

 

 

parameter setup.

 

 

 

 

Depress the “Next Page” button.

 

 

 

 

At the end of the parameter

 

 

 

 

setup mode, you will be prompt-

 

 

 

 

ed to save the settings.

 

 

 

 

To save the settings press the

 

 

 

 

“Confirm” button. If you do not

 

 

 

 

wish to save the settings, press

 

 

 

 

the Off / Bypass button for five

 

 

 

 

seconds. The LCD will display

 

 

 

 

OFF to indicate the

 

 

 

 

settings are not saved.

IMPORTANT:

 

The UPS must be switched to maintenance bypass mode, shut down and restarted after

 

 

entering

30

Page 30
Image 30
Falcon FN3KRM-2TXI, FN4KRM-2TXI, FN6KRM-2TXI manual Shows the UPS unit address. If