6.2.5 Map Descriptor Example 1 - Explicit Configuration using Network Management Polls
The Map Descriptor pollTemp_p shows the use of SNVT_Units for Scaling when polling temperature
The Map Descriptor pollSwitch shows the use of SNVT_Option for Selective data scanning. This only brings in the “State” portion of SNVT_Switch
Map_Descriptors  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
Map_Descriptor_Name  | ,Data_Array_Name  | ,Data_Array_Offset  | ,Lon_Function  | ,Function  | ,Node_Name  | ,SNVT_Index  | ,SNVT_Type  | ,SNVT_Units  | ,SNVT_Option  | ,Scan_Interval  | 
pollTemp_p  | ,DA_Explicit  | ,1  | ,NMFETCHC  | ,Rdbc  | ,Remote_Node  | ,0  | ,SNVT_temp_p  | ,Deg_F  | ,-  | ,1.0s  | 
pollSwitch  | ,DA_Explicit  | ,2  | ,NMFETCHC  | ,Rdbc  | ,Remote_Node  | ,1  | ,SNVT_switch  | ,-  | ,State  | ,1.0s  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
This field  | 
  | 
  | 
determines the  | 
  | 
  | 
Map  | Explicitly Addressed Client Map Descriptors use  | For   | 
Descriptor’s  | this field to point to their relevant Server Map  | Client Map  | 
function. See  | Descriptors.  | Descriptors the  | 
Section 6.1.2  | 
  | Scan_Interval  | 
for more  | 
  | determines the  | 
information.  | 
  | update rate.  | 
6.2.6 Map Descriptor Example 2 – Polling UNVT’s
Map_Descriptors  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
Map_Descriptor_Name  | ,Data_Array_Name  | ,Data_Array_Offset  | ,Lon_Function  | ,Function  | ,Node_Name  | ,SNVT_Index  | ,SNVT_Type  | ,UNVT_Byte_Length  | ,Scan_Interval  | 
pollUNVT  | ,DA_Explicit  | ,101  | ,NMFETCHC  | ,Rdbc  | ,Remote_Node  | ,2  | ,UNVT  | ,31  | ,1.0s  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
UNVT Byte length must be specified for correct operation.