FS-8700-21 LonWorks Manual Page 37 of 62
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com
Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: support@fieldserver.com
SNVT_alarm
Data Length
25
Suggested Data Array Formats
Uint16, Float
Data Item 1-6
Alm_Location00,
..Alm_Location05
Measurement
Units
Values Range
Invalid Value
Location array element
8-bit unsigned byte
0 .. 255
N/A
Data Item 7
Object_ID
Measurement
Units
Values Range
Invalid Value
Object ID
object index
0 .. 65,535
N/A
Data Item 8
Alarm_type
Measurement
Units
Values Range
Invalid Value
alarm_type_t
N/A
0 .. 254
255 (0xFF)(AL_NUL)
Data Item 9
Priority_level
Measurement
Units
Values Range
Invalid Value
Priority_level_t
N/A
0 .. 11
255 (0xFF)(PR_NUL)
Data Item 10
Index_to_SNVT
Measurement
Units
Values Range
Invalid Value
Index to NV
index of NV causing
alarm
0 .. 65,535
N/A
Data Item 11-14
Alm_Value00,
..Alm_Value03
Measurement
Units
Values Range
Invalid Value
Value array element
specific to NVT
0 .. 255
N/A
Data Item 15
Year
Measurement
Units
Values Range
Invalid Value
Year
year
0 .. 3000
N/A
Data Item 16
Month
Measurement
Units
Values Range
Invalid Value
Month
month of year
0 ..12
N/A
Data Item 17
Day
Measurement
Units
Values Range
Invalid Value
Day
day of month
0 ..31
N/A
Data Item 18
Hour
Measurement
Units
Values Range
Invalid Value
Hour
Hour of day
0 ..23
N/A
Data Item 19
Minute
Measurement
Units
Values Range
Invalid Value
Minute
Minutes
0 ..59
N/A
Data Item 20
Second
Measurement
Units
Values Range
Invalid Value
Second
Seconds
0 ..59
N/A
Data Item 21
Millisecond
Measurement
Units
Values Range
Invalid Value
Millisecond
Milliseconds
0 ..999
N/A
Data Item 22-25
Alm_limit00, ..Alm_limit03
Measurement
Units
Values Range
Invalid Value
Alarm limit array
element
specific to NVT
0 .. 255
N/A
SNVT_amp
Data Length
1
Suggested Data Array Formats
Float
Data Item 1
Measurement
Units
Values Range
Invalid Value
Electric current
Amperes
-3,276.8...
3,276.7
N/A