FieldServer FS-8700-21 instruction manual Using Neuron ID to Address Devices Client Drivers only

Models: FS-8700-21

1 62
Download 62 pages 42.76 Kb
Page 20
Image 20

FS-8700-21 LonWorks Manual

Page 20 of 62

 

 

6.2.7 Using Neuron ID to Address Devices (Client Drivers only)

It is possible to poll remote LonWorks devices using their Neuron ID's instead of the traditional Network Manager method. The Neuron ID is the 12 Digit Hex identifier of the associated LonWorks Device. An example configuration follows.

Note that Neuron ID addressing is considered explicit addressing so the station address, domain ID and subnet ID must be set as described in Section 6.1.4

Bridge

System_Station_Address ,Title

110

,":D01:S01:Neuron ID Example:"

 

 

On the Client side Nodes add a new field as shown below:

Nodes

 

 

 

 

 

 

 

 

 

 

 

Node_Name

,Node_ID

,Protocol

,Neuron_ID

 

 

 

 

 

 

 

Lon_Srv_11

,11

,Lonworks

,F912AB440100

 

 

 

 

 

 

 

Create a Map Descriptor as Follows:

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Map_Descriptors

 

 

 

 

 

 

 

 

 

 

Map_Descriptor_Name

,Data_Array_Name

,Data_Array_Offset

,Lon_Function

,Function

,Node_Name

,SNVT_Index

,SNVT_Type

,Scan_Interval

1nviAmp1

,DA_001

 

,0

 

,NMFETCHC

,RDBC

,Lon_Srv_11

,000

,SNVT_amp

,0s

 

 

 

 

 

 

 

 

 

 

 

 

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: support@fieldserver.com