FieldServer FS-8700-21 instruction manual Cfgnvui

Models: FS-8700-21

1 62
Download 62 pages 42.76 Kb
Page 26
Image 26

FS-8700-21 LonWorks Manual

Page 26 of 62

 

 

LonMark Config file Example #1 – Open Loop “Water Temperature” Sensor:

 

// Client Side Map Descriptors

 

 

 

 

 

 

 

 

 

 

Map_Descriptors

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Map_Descriptor_Name

,Data_Array_Name

,Data_Array_Offset

,Lon_Function

,Function

,Node_Name

,SNVT_Index

,SNVT_Type

,Nv_Min_Value

,Nv_Max_Value

,Nv_Selfdoc_text

 

nvoTemp

,DA_FI_01

,0

,NVUOIMC

,Wrbc

,LON_1

,-

,SNVT_Temp_f

,-

,-

,“@01;WaterTemp”

 

NviTempMin

,-

,-

,CFG_NVUI

,Server

,LON_1

,-

,SNVT_Temp_f

,10

,-

,“&200\x8023”

 

NviTempMax

,-

,-

,CFG_NVUI

,Server

,LON_1

,-

,SNVT_Temp_f

,-

,300

,“&200\x8020”

 

 

 

 

 

 

 

 

 

 

 

 

The Node Self- Documentation String defines one LonMark object of type 1 – Open Loop Sensor.

These two configuration network variables will be linked to the first Map Descriptor declared. The NV_Min_Value and NV_Max_Value fields define the defaults for these CP’s. These defaults are loaded by the FieldServer after a restart only when re-commissioning is required.

The object index is 0 and this Map Descriptor defines the 1st Network Variable of the object.

LonMark Config file Example #2 – “Water Heating Element” Actuator:

 

// Client Side Map Descriptors

 

 

 

 

 

 

 

 

 

 

Map_Descriptors

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Map_Descriptor_Name

,Data_Array_Name

,Data_Array_Offset

,Lon_Function

,Function

,Node_Name

,SNVT_Index

,SNVT_Type

,Nv_Min_Value

,Nv_Max_Value

,Nv_Selfdoc_text

 

nvoTemp

,DA_FI_01

,0

,NVUOIMC

,Wrbc

,LON_1

,-

,SNVT_Temp_f

,-

,-

,“@01;WaterTemp”

 

NviTempMin

,-

,-

,CFG_NVUI

,Server

,LON_1

,-

,SNVT_Temp_f

,10

,-

,“&200\x8023”

 

NviTempMax

,-

,-

,CFG_NVUI

,Server

,LON_1

,-

,SNVT_Temp_f

,-

,300

,“&200\x8020”

 

 

 

 

 

 

 

 

 

 

 

 

The Node Self- Documentation String defines one LonMark object of type 3 – Open Loop Actuator.

These two configuration network variables will be linked to the first Map Descriptor declared. The NV_Min_Value and NV_Max_Value fields define the defaults for these CP’s. These defaults are loaded by the FieldServer after a restart only when re- commissioning is required.

The object index is 0 and this Map Descriptor defines the 1st Network Variable of the object.

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: support@fieldserver.com

Page 26
Image 26
FieldServer FS-8700-21 instruction manual Cfgnvui