Appendix B.2. Neuron Systems

Newron Systems may produce the following Error message “bindings lost after power-cycle” The solution to this is to place the FieldServer in the Configured state which will cause the bindings to be committed to the Neuron and they will remain after a power cycle.

Procedure:

1)Make the bindings in NL220

2)Place devices in ONLINE mode or state.

3)Refer to the following Screencap for assistance in placing the FieldServer in the Configured state.

Appendix B.3. Honeywell Care

This system uses unacknowledged service as default. This protocol driver requires acknowledged service to operate correctly.

Appendix B.4. Tridium JACE

This system uses unacknowledged service as default. This protocol driver requires acknowledged service to operate correctly.

Note that Tridium calls Acknowledged service “critical bindings”.