FieldServer FS-8700-21 instruction manual Appendix A.9. Filtering Snvt Variables

Models: FS-8700-21

1 62
Download 62 pages 42.76 Kb
Page 28
Image 28

FS-8700-21 LonWorks ManualPage 28 of 62

Appendix A.9. Filtering SNVT Variables

Appendix A.9.1.

SNVT_Option Field

This field can be used to isolate a specific record within a complex SNVT. Appendix D shows which SNVTs are currently attributed with SNVT_Option capabilities.

Appendix A.9.2.

SNVT_Units Field

The measurement units of a SNVT is fixed as far as it is transported across the LonWorks network, but by the setting of the SNVT_Units field it is possible to specify how the data is made available in Data Arrays. For example SNVT_temp_f is always transported across the LonWorks network as degrees Celsius, but by setting the SNVT_Units field to Deg_F the measurement units of the Map Descriptor’s data will be set to degrees Fahrenheit. The following table shows which SNVT’s currently have SNVT_Units capabilities.

SNVT_Type

SNVT_Option

SNVT_UnitsLength

Measurement Units

SNVT_press_f

N/A

Inch_H20

1

Inches of water

 

 

 

 

 

SNVT_press_p

N/A

Inch_H20

1

Inches of water

 

 

 

 

 

 

 

Raw

1

Raw, unadjusted data

 

 

 

 

 

SNVT_temp

N/A

Deg_C

1

Degrees Celsius (°C)

 

 

 

 

 

 

 

Deg_F

1

Degrees Fahrenheit (°F)

 

 

 

 

 

SNVT_temp_f

N/A

Deg_C

1

Degrees Celsius (°C)

 

 

 

Deg_F

1

Degrees Fahrenheit (°F)

 

 

 

 

 

 

 

 

 

Raw

1

Raw, unadjusted data

 

 

 

 

 

SNVT_temp_p

N/A

Deg_C

1

Degrees Celsius (°C)

 

 

 

 

 

 

 

Deg_F

1

Degrees Fahrenheit (°F)

 

 

 

 

 

 

All

Raw

2

Raw, unadjusted data

 

 

 

 

 

SNVT_switch1

Value

Raw

1

Raw, unadjusted data

 

 

 

Percent

1

Percent (%)

 

 

 

 

 

 

 

 

State

Raw

1

Raw, unadjusted data

 

 

 

 

 

1See Also Appendix A.8

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: support@fieldserver.com