Appendix C. Troubleshooting Tips Appendix C.1. Debugging a LonWorks connection: Hints and tips
To test connections, set the configuration tool into a mode that will display service requests, and then
push the button on the FieldServer. A request should appear.
In order for variables to appear as outputs, they need to be declared as write variables in the FieldServer.
Declaring the Map Descriptor functions as WRBC, or WRBX can do this. See S ection 5.1.2 for more
information.
If the domain and Subnet ID are defined in the configuration file of the FieldS erver, these value s will be
used when power is cycled to the FieldServer. If the values set here are different to what the Network
Manager has set up for the FieldServer for clients using implicit addressing, the FieldServer will stop
communicating. In this case, chan ge these settings o r remove the m from the configuration file
completely and recommission the FieldServer.
Appendix C.2. Error Messages
Message
Description
"LON:#03 FYI. Standard driver build. This is normal.
This message is informational and can be safely ignored.
Appendix C.2.1. Err or M ess age Lonl ive .c 1 21
If the following error message is returned:
DRIVER-> LON : Error, timeout while waiting for Lon I/F to reset!-------- Configuration Error ------
It is possible that th e FieldServer hardware in use may not support LonWorks, or the firmware loaded contains
LonWorks but is the wrong firmware for the application. Remove LonWorks from the configuration or get new
firmware/hardware.