CHAPTER 2 - Installation
Installation of the DX40 Unit
DX40 Serial Device Router Installation Guide
16
Figure 2-5. Ground and Power Connections
Making the Ground Connection
The ground wire should be 14 AWG terminated with a #6 ring lug.
Make the facility ground connection as follows:
1.Loosen the ground screw on the chassis, insert the #6 ring lug, and tighten the
ground screw.
2.Connect the other end of the ground wire to the facility ground.
ELECTRICAL WARNING:Verify that a proper ground connection is made from the
grounding screw to facility ground prior to connecting power to the DX40. Failure to have
a proper ground path could cause serious injury or death to personnel in cases of power
surges.
non-polarized
90-250V
~ or
0.2A;50-60Hz
Serial No:
0650 0034
DX40-01-H-D
Non-polarized power input.
Grounding screw