3.4.5 Configuration page

In this page, the SNMP/Web adapter configuration file is shown in a text area. The configuration file can
be exported by pressing the Highlight button and copying the selected text (e.g. CTRL+C) to a separate
application.

3.4.6 Upgrade page

This page shall only be accessed when the SNMP/Web adapter SW is to be upgraded. Refer to the
section for details on the SW upgrade process.
NOTE: Use only GE officially released SW. Only perform the SW upgrade when requested to do so by GE.
3.5 SNMP SECTION
The SNMP section deals with SNMP and trap configuration.

3.5.1 SNMP settings page

The most relevant SNMP settings are the following:
Parameter Name Description
Set SNMP server listening port. Default port is 161. Port Number
Defines the community name for receiving SNMP information (GET). The get
community name controls access to the SNMP Agent – the community in the
request must match the getcommunity parameter.
The default value is public.
Get Community
Defines the community name for writing SNMP information (SET). The set
community name controls access to the SNMP Agent – the community in the
request must match the setcommunity parameter. The default value is private.
Set Community

3.5.2 Trap settings page

This page allows to configure up to 20 recipients of SNMP traps. The most relevant settings are the
following:
Parameter Name Description
IP-address of the trap target Trap destination
Community name (optional – default is public) Community
Controls SNMP trap version:
If unchecked, v1 traps are sent (default)
If checked, V2 traps are sent
V2
Port to which the trap will be sent (optional – default 162) Port

3.5.3 Alarm notification page

This page is used to configure the alarm notification via trap and/or e-mail. Every alarm is listed, and the
user may enable the notification via trap and/or e-mail upon alarm (de)activation.
Modifications reserved Page 32/58