3.3.2 Battery page

The Battery page shows the following information.

Parameter Name Description
The current status of the battery:
1 – unknown
Battery Status
2 – normal The remaining run-time on batteries is greater than
the UPS low battery time (ref. UPS Config page)
3 – low The remaining run-time is less than or equal the UPS low
battery time (ref. UPS Config page)
4 – depleted The battery would be unable to sustain the load, if mains
power is lost
Seconds On Battery The time elapsed since the UPS switched to battery power (in seconds)
Estimated Minutes Remaining An estimate of the remaining run-time on batteries, under present load
conditions (in minutes)
An estimate of the remaining battery charge (in percentage – 100% is full
charge)
Estimated Charge Remaining
The present battery voltage (in Volts) Battery Voltage
The battery flowing from/to the battery (in Amperes) Battery Current
The ambient temperature of the UPS batteries (in °C) Battery Temperature
The RSM ripple on the DC link (in Vrms) Battery Ripple