3.3.6 UPS Test page 3.3.7 UPS Control page (1-ph/SP units ONLY) 3.3.8 UPS Config page
This page presents allows to initiate a specific UPS test, and reports the status of the last performed test
(if any). The page includes a table with clear explanation of the test result reading.
For an explanation of the various test procedures please refer to the applicable UPS documentation.
The UPS control page mainly controls UPS shutdown and reboot behaviour. As previously stated, these
commands will impact the UPS and may have effect on any load applied to the UPS. It is therefore
important to fully understand the consequences of any settings performed through this page.
Parameter Name Description
Shutdown type The action to be taken when the UPS is commanded to shutdown
1 – output The output of the UPS is switched off
2 – system The entire UPS system is switched off
Shutdown after delay Specifies a time (in seconds) after which the UPS will shutdown
-1 disables the procedure
0 immediate shutdown
Specifies a time (in seconds) after which the UPS will start-up Startup after delay
-1 disables the procedure
0 immediate start-up
The UPS will shutdown immediately, and will remain off for the specified time (in
seconds), after which the UPS will restart
Reboot
-1 disables the procedure
On – the UPS will restart right after the shutdown Auto-Restart
Off – the UPS will not restart after the shutdown
Caution! These commands may switch off the UPS output, therefore leaving the load with no power.
Make sure you fully understand the effect on the UPS and on the load before injecting any of these
commands. Make sure that it is safe to perform the described operation for both the UPS and the load.
The page lists the main UPS configuration parameters. Normally, these parameters are pre-configured
at the factory and there is no need to change them. Furethermore, forcing an incorrect configuration
may impair the UPS functionalities and severly affect the load. It is therefore recommended not to alter
any configuration settings unless informed and instructed to do so.
Modifications reserved Page 30/58
OPM_CNT_SNM_BAS_CRD_1GB_V012.doc Operating Manual SNMP/Web Adapter