NEC SECTION 210-20 (a)

Table 310-16. Allowable Ampacities of Insulated Conductors Rated O Through 2000 Volts, 60°C Trough 90°C (140°F Trough 194°F) Not More than Three Current-Carrying Conductors in Raceway, Cable, or Earth (Directly Buried), Based on Ambient Temperature of 30°C (86°F).

 

Size

 

Temperature Rating of Conductor (See table 310-13)

 

 

 

60°C (140°F)

75°C (167°F)

90°C (194°F)

60°C (140°F)

75°C (167°F)

90°C (194°F)

 

 

Types

Types

Types

Types

Types

Types

 

 

TW, UF

FEPW, RH,

TBS, SA, SIS,

TW, UF

RH, RHW,

TBS, SA, SIS,

 

 

 

RHW, THHW,

FEP, FEPB, MI,

 

THHW,

THHN, THHW,

 

AWG

 

THW, THWN,

RHH, RHW-2,

 

THW, THWN,

THW-2,

 

or

 

XHHW, USE,

THHN, THHW,

 

XHHW, USE

THWN-2, RHH,

 

kcmil

 

ZW

THW-2,

 

 

RHW-2, USE-2,

 

 

 

 

THWN-2, USE-2,

 

 

XHH, XHHW,

 

 

 

 

XHH, XHHW,

 

 

XHHW-2,

 

 

 

 

XHHW-2,ZW-2

 

 

ZW-2

 

 

 

COPPER

 

ALUMINUM or COPPER-CLAD ALUMINUM

 

18

---

---

14

---

---

---

 

16

---

---

18

---

---

---

 

14

20

20

25

---

---

---

 

12

25

25

30

20

20

25

 

10

30

35

40

25

30

35

 

8

40

50

55

30

40

45

 

6

55

65

75

40

50

60

 

4

70

85

95

55

65

75

 

3

85

100

110

65

75

85

 

2

95

115

130

75

90

100

 

1

110

130

150

85

100

115

 

1/0

125

150

170

100

120

135

 

2/0

145

175

195

115

135

150

 

3/0

165

200

225

130

155

175

 

4/0

195

230

260

150

180

205

 

250

215

255

290

170

205

230

 

300

240

285

320

190

230

255

 

350

260

310

350

210

250

280

 

400

280

335

380

225

270

305

 

500

320

380

430

260

310

350

 

600

355

420

475

285

340

385

 

700

385

460

520

310

375

420

 

750

400

475

535

320

385

435

 

800

410

490

555

330

395

450

 

900

435

520

585

355

425

480

 

1000

455

545

615

375

445

500

 

1250

495

590

665

405

485

545

 

1500

520

625

705

435

520

585

 

1750

545

650

735

455

545

615

 

2000

560

665

750

470

560

630

 

 

 

 

CORRECTION FACTORS

 

 

 

Ambient

For ambient temperatures other than 30°C (86°F), multiply the allowable ampacities shown above by the

 

Temp. (°C)

 

 

appropriate factor below

 

 

 

21 - 25

1.08

1.05

1.04

1.08

1.05

1.04

 

26 - 30

1.00

1.00

1.00

1.00

1.00

1.00

 

31 - 35

0.91

0.94

0.96

0.91

0.94

0.96

 

36 - 40

0.82

0.88

0.91

0.82

0.88

0.91

 

41 - 45

0.71

0.82

0.87

0.71

0.82

0.87

 

46 - 50

0.58

0.75

0.82

0.58

0.75

0.82

 

51 - 55

0.41

0.67

0.76

0.41

0.67

0.76

OPM_SGS_ISG_M22_M30_0US_V011.doc

20/38

Installation Guide SG Series 225 & 300 kVA