g

GE

In case of parallel system, try to place the UPS modules in sequence of their numbers (marked on the packing).

If the units are positioned “side

SGS_225-300_RPA disposition_GE_01US

UPS 2

UPS

3-4-5-6-7-8

by side”, the side panels must be mounted on all units.

UPS 1

Fig. 3.4.1-5 RPA system disposition

3.4.2Battery location

Batteries require a well-ventilated room with controlled temperature to obtain reliable operation.

The Battery can be install immediately adjacent to the UPS (left or right side) or remotely from the UPS.

If the Battery is installed remotely from the UPS, a wall mounted DC disconnect device must be installed within line-of-site to both the UPS and the Battery.

The optimal room temperature for the Battery is 68°F (20°C) to 77°F (25°C).

The life of valve-regulated batteries will be reduced by 50% for each additional 18°F (10°C) that the Battery ambient temperature is above 77°F (25°C).

The Battery System associated with larger UPS is usually either rack mounted or installed in multiple Battery Cabinets.

Installation and assembly must be made according to the local standards and Battery System manufacturer‘s recommendations.

The Battery Circuit Breaker or Battery Fuse Box must be mounted as near as possible to the Battery.

Battery installation and connection must be performed by qualified personnel only.

Read all safety instructions before proceeding with the installation.

OPM_SGS_ISG_M22_M30_0US_V011.doc

14/38

Installation Guide SG Series 225 & 300 kVA

Page 14
Image 14
GE 225, 300 manual Battery location, RPA system disposition