Installation Instructions
230/208 VOLT ELECTRICAL CONNECTION OPTIONS1.Remove the room cabinet.
2.Connect to electrical power.
3.Review the following steps for applicable supply voltages.
4.Reinstall the room cabinet.
Power cords may include an arc fault interruption or a leakage current detection interruption device. A test and reset button is provided on the plug case or the inline case. The device should be tested on a periodic basis by first pressing the TEST button and then the RESET button. If the TEST button does not trip or if the RESET button will not stay engaged, discontinue use of the Zoneline and contact a qualified service technician.
A powersupply kit withLCDI must be usedto supplypower to the Zonelineunit.Theappropriatekit is determinedby the voltage, the means of electricalconnectionand
the amperage of the branch circuit.
Appearance may vary.
Power supply kit
Connectionsof 208 or
All wiring, including installation of the receptacle, must be in accordance with the NEC and local codes, ordinances and regulations. Codes require the use of an arc fault or leakage current detection device on the power cord except direct connect. Be sure to select the correct cord for your installation.
Tandem | Perpendicular | Large Tandem | |||
15 Amp. | 20 Amp. |
| 30 Amp. | ||
|
|
|
| ||
Branch Circuit and |
| Proper GE Power Cord | |||
Unit AmperageRating |
|
| with LCDIDevice | ||
|
|
|
|
|
|
| 15 |
|
| RAK3153 | |
|
|
|
|
|
|
| 20 |
|
| RAK3203 | |
|
|
|
|
|
|
| 30 |
|
| RAK3303* | |
|
|
|
|
|
|
*Not approved for use on 7000 BTU models.
CONNECTION
Branch Circuitand | Proper GE | |
UnitAmperage Rating | Subbase Kit | |
|
|
|
15 | RAK204D15P | |
|
|
|
20 | RAK204D20P | |
|
|
|
30 | RAK204D30P* | |
|
|
|
*Not approvedfor use on 7000 BTUmodels.
Electrical subbases provide an enclosurefor direct connection or enclosed receptacles. The subbase kit includes the power cord.
The instructions provided with the selected subbase kit must be carefully followed. It is the responsibility of the installer to ensure the connection of components is done in accordance with these instructions and all electrical codes.
DIRECT CONNECTIONOrder the following Kit for
Branch Circuitand | Power Supply | Power | |
UnitAmperage Rating | Accessory | Supply Kit | |
|
|
|
|
15 | RAK4002A | RAK4157 | |
|
|
|
|
20 | RAK4002A | RAK4207 | |
|
|
|
|
30 | RAK4002A | RAK4307* | |
|
|
|
|
*Not approved for use on 7000 BTU models.
Skip to the “MAKE ELECTRICAL CONNECTION TO THE UNIT” section.