Installation Instructions

265 VOLT ELECTRICAL CONNECTION OPTIONS

WARNING:

Connectionof this 265V AC product to a branchcircuit MUST be done by direct connection in accordancewith the NationalElectrical Code. Plugging this unit into a building-mountedexposed receptacle is not permitted by code.

These models must be installed using the appropriate GE powersupplykit for the branch circuit amperage and the electrical resistanceheater wattage desired. Use the POWER CONNECTION CHART on page 16 to determine the correct kit required.One of the following installation methods (A or B) must be used.

A. FORSUBBASE INSTALLATION

Electrical subbasekits are availableto provide a flexible enclosure for direct connection.

Branch Circuit and

Proper GE

Power

Unit AmperageRating

Subbase KitSupplyKit

 

 

 

15

RAK204E15

RAK5172

 

 

 

20

RAK204E20

RAK5202

 

 

 

30

RAK204E30

RAK5302*

 

 

 

*Not approvedfor use on 7000 BTUmodels.

The instructionsprovided with the selected subbase kit must be carefullyfollowed.It is the responsibilityof the installer to ensure the connection of componentsis done in accordance with these instructions and all electrical codes.

B. FOR DIRECTCONNECT

INSTALLATION

If an electrical subbase is not used, direct connection to branch circuit wiring inside the provided junction box must be done in accordance with the following steps.

Order the following Kit for 265-volt direct connection as required:

Branch Circuitand

Power

UnitAmperage Rating

Supply Kit

 

 

 

15

RAK5157

 

 

 

20

RAK5207

 

 

 

30

RAK5307*

 

 

 

*Not approved for use on 7000 BTU models.

Proceed to the “MAKE ELECTRICAL CONNECTION TO THE UNIT” section.

NOTE: Order Kit RAK4002CW to enable a quick disconnect inside the junction box.

14