Auxiliary controls on yourZoneline.
External Fan (Obtained locally)Whenconnected, an auxiliary or externalfan can be controlled with the indoor fan motor on the Zoneline. Connections provide 24 V AC to energizea remoterelay, turningon the externalfan.
Central Desk ControlWhenconnected, the unit can be turnedONor OFF with a switch locatedat the CentralControl Panel.A separate wire pair must be run from eachseparate controlling switchto eachindividual Zoneline.
Referto MODE 2 on page5 for fan settingoptions.
RemoteThermostatWhenconnectedto a remote thermostat, the indoorair temperature sensingis shifted from the unitto the remote thermostat. For this reason,the units will operate slightly differently when connected to a remote thermostat. The following chartshows the unitoperation when connected to a remote thermostat.
NOTE: The Class2 Mode setting (Mode 6) mustbe set to ON " " for the unitto operate with a Class2 Remote Wall Thermostat. (See the installation instructions supplied with the remotethermostat and Mode instructions on page7.)
Troubleshooting Tips
Class 2 Shown ON
IMPORTANT: The Zoneline thermostat connectionsprovide 24 V AC only.
If using a digital/electronic wall thermostat, you mustset it to the 24 V ACsetting.See the InstallationInstructions for the wall thermostat.
Damage to a wall thermostat or to the Zoneline electronicscan resultfromimproperconnections. Special care must be usedin connecting the wires.No line voltageconnectionsshould be made to any circuit. Isolateall wires in buildingfrom linevoltage.
Consumer Support
| Feature | Heat Pump | Electric Heat |
| Indoor Frost Control | Yes | Yes |
| Freeze Sentinel | Yes | Yes |
| Auto Fan Speed | No | No |
| Electronic Temperature Limiting | No | No |
| Switch to Resistance Heat Based | Determined by | N/A |
| On Indoor Temperature | Remote Thermostat |
|
| Switch to Resistance Heat Based | Yes | N/A |
| On Outdoor Temperature |
|
|
| Reverse Cycle Defrost | Yes | N/A |
| Simultaneous Resistance Heat | No | N/A |
| with Heat Pump |
|
|
| Resistance Heat Lockout | Yes | N/A |
| “Smart Fan” Fan Cycle | Fan ON/AUTO Set On | Fan ON/AUTO Set On |
|
| Remote Thermostat | Remote Thermostat |
8 | Central Desk Control | Yes | Yes |