Table 1 BECO2200 DCA Configuration Tables

 

BECCO2200 DCA

GE Energy Services

Configuration Guide

Table 1 BECO2200 DCA Configuration Tables

1.2Configuration Sequence

The following is a list of the steps required to configure the BECO2200 DCA:

1.Edit the A164 configuration. Prepare it according to the guidelines in this document and the specific use for which the BECO2200 DCA is required.

2.Edit the configuration for all other applications that will run on the product. Prepare them according to their own configuration guides.

3.Generate the configuration and download it to the product using the GE Energy Services Configuration System provided. The list of applications to be compiled must include A164.

4.Restart the product. The BECO2200 DCA will check the validity of its configuration parameters and begin its initialization. If it determines that a configuration parameter is incorrect or encounters an error during its initialization, it will log a message to the WESMAINT Error Log and then, depending on the severity of the error, terminate or continue with its run-time function. Self-termination of the BECO2200 DCA prevents it from running using invalid data.

5.Check for error messages. Log into the WESMAINT maintenance interface, select the

System Functions item from the Main Menu, and then select the Error Log item from the System Functions Menu. If any error messages are displayed, correct the problem as described in Appendix A: Messages Logged by the BECO2200 , and repeat steps 3 through 5.

Configuration is complete when the BECO2200 DCA has successfully validated all configuration parameters.

A164-0CG-1.00-2Restricted