BECCO2200 DCA

 

Configuration Guide

GE Energy Services

F105: Invalid SOE Overflow parameter

Cause:

The SOE Buffer Overflow Option configuration parameter in the A164APPL table is neither Overwrite Oldest (0) nor Discard Newest (1).

Remedy:

·Review the section on configuring the A164APPL table (Chapter 3:) and verify that the SOE Buffer Overflow Option is configured correctly.

F106: Total # devices exceeds UNIT size

Cause:

The sum of all BECO2200 devices specified in all records of the A164PORT table is greater than the number of records in the A164UNIT table.

Remedy:

Address all fatal and non-fatal error messages preceding this message.

Review the section on configuring the A164PORT table (Chapter 4:) and verify that the Number of Devices on Port configuration parameter in each record is correct.

Verify the sum of all Number of Devices on Port configuration parameters is less than or equal to the number of records in the A164UNIT table.

F107: <x> WESDAC_<y> pnts configured, <z> required

Cause:

<x> number of WESDAC_<y> points were configured in the WIN CFG_DCA table for the BECO2200 DCA. <z> points are required.

Remedy:

Review the section on configuring WIN for the BECO2200 DCA (Chapter 2:) and verify that the number of WESDAC_<y> points configured for the BECO2200 DCA is greater than or equal to <z>.

WESDAC NUMBER

DATA TYPE

 

 

WESDAC_1

Binary Input

 

 

WESDAC_2

Binary Output

 

 

WESDAC_3

Counter

 

 

WESDAC_4

Analog Input

 

 

WESDAC_5

Analog Output

 

 

WESDAC_6

Device Status

 

 

 

 

Table 10 WESDAC Number Definitions

Restricted

A164-0CG-1.00-2

Full

27

 

Page 43
Image 43
GE BECCO2200 manual F105 Invalid SOE Overflow parameter, F106 Total # devices exceeds Unit size