8.2.1 Table Type

This parameter specifies the table type of the BECO2200 to write the data value. Valid Type number is zero (0), one (1), two (2), and eight (8).

8.2.2 Point Number

This parameter specifies the point number of the table type of the BECO2200 to write the data value. For M-0420 relay the valid points are as follows:

Type 0: Points 14-23,26-28,70-73

Type 1: Points 0-17,19,21-26 ,28-31

Type 2: Points 1-9,13-18,20-23,25-28,30-32,34,38-41,45-52,57-65,69

Type 8: Points 5

8.2.3 Data Value

This parameter specifies the value to be written to the data table of the BECO2200 Multifunction Relay.

NOTE: The configured value is the value that will be written to the unit. No scaling by the BECO2200 DCA will occur.