W608: Error <x> on WES<y> INIT_POINT win write

 

BECCO2200 DCA

GE Energy Services

Configuration Guide

W608: Error <x> on WES<y> INIT_POINT win write

W609: Error <x> on WES6 CHANGE_TRANS win write

W610: Error <x> on WES6 CHANGE_FAILS win write

W611: Error <x> on WES6 CHANGE_RETRIES win write

W612: Error <x> on WES1 DATA_CHANGE win write

W613: Error <x> on WES<y> TT DATA CHANGE win write

A.4 Information Messages

Information messages are posted when the BECO2200 DCA encounters a situation where it must, as a result, perform some action. Expressions in angular brackets like “<x>”, are filled with the appropriate values by the BECO2200 DCA. Each information message is given a unique identification number, within the range of I700 through I799.

I700: PORT rec <x>, invalid reply time-out

Cause:

Record <x> of the A164PORT table contains a Remote Reply Timeout that is less than the amount of time required to receive the maximum message length.

Effect:

The BECO2200 DCA will set this parameter to the minimum time required to receive the maximum message length.

Remedy:

Review the section on configuring the A164PORT table (Chapter 4:), and configure the Remote Reply Timeout to at least the time required to receive the maximum message length.

I701: PORT rec <x>, invalid RTS on time

Cause:

Record <x> of the A164PORT table contains a RTS On Time that is less than one.

Effect:

The BECO2200 DCA will set this parameter to one.

Remedy:

If modem signals are required, review the section on configuring the A164PORT table (Chapter 4:) and verify the RTS On Time is a valid time.

If modem signals are not required, set this parameter and the RTS Off Time to zero.

I702: PORT rec <x>, invalid RTS off time

Cause:

Record <x> of the A164PORT table contains a RTS Off Time that is less than one character time.