A.2 Non-Fatal Error Messages

 

BECCO2200 DCA

GE Energy Services

Configuration Guide

A.2 Non-Fatal Error Messages

Non-fatal errors cause the offending process to log a message to the WESMAINT Error Log and suspend without affecting the rest of the BECO2200 DCA. For example, if a single polling process encounters a non-fatal error, no polling will occur on the associated communication port. However, demand scans on the communication port will still be an available option.

This section contains a description of all these non-fatal errors. Expressions in angular brackets like “<x>”, are filled with the appropriate values by the BECO2200 DCA. Each non-fatal error message contains a unique identification number, within the range of E300 through E499.

E300: PORT rec <x>, invalid baud rate

Cause:

Record <x> of the A164PORT table contains an invalid Baud Rate.

Effect:

Communication to all BECO2200 devices configured to use this port will be unavailable.

Remedy:

Review the section on configuring the A164PORT table (Chapter 4:), and verify that the Baud Rate configuration parameter is configured as either 110, 300, 600, 1200, 2400, 4800, or 9600.

E301: PORT rec <x>, invalid failures before offline

Cause:

Record <x> of the A164PORT table contains an invalid Failures Before Offline.

Effect:

Communication to all BECO2200 devices configured to use this port will be unavailable.

Remedy:

Review the section on configuring the A164PORT table (Chapter 4:), and verify that the Failures Before Off-line configuration parameter is greater than zero.

E302: PORT rec <x>, num of devices exceeds UNIT

Cause:

The Number of Devices on Port parameter in record <x> of the A164PORT table is greater than the number of records in the A164UNIT table.

Effect:

Communication to all BECO2200 devices configured to use this port will be unavailable.

Remedy:

Review the section on configuring the A164PORT table (Chapter 4:), and verify that the Number of Devices on Port is correct.