E303: PORT rec <x>, configuration bad

Cause:

The BECO2200 DCA encounter non-fatal errors in record <x> of the A164PORT table.

Effect:

Communication to all BECO2200 devices configured to use this port will be unavailable.

Remedy:

Address all non-fatal errors preceding this message.

E304: PORT rec <x>, invalid unit address

Cause:

Record <x> of the A164PORT table contains an invalid Unit Address.

Effect:

Communication to all BECO2200 devices configured to use this port will be unavailable.

Remedy:

Review the section on configuring the A164PORT table (Chapter 4:), and verify that the Unit Address configuration parameter is within the range of 0 through 255.

E305: UNIT rec <x>, invalid unit type

Cause:

Record <x> of the A164UNIT table contains an invalid Unit Type.

Effect:

Communication to this unit will be unavailable.

Remedy:

Review the section on configuring the BECO2200 DCA A164UNIT Configuration Table (Chapter 5:), and verify that the Unit Type is BECO2200-M-0420 (0)

E306: Unit <x> and <y>, same address on port <z>

Cause:

Two BECO2200 devices have been configured with the same address on port <z>.

Effect:

Communication to the two devices will be unavailable.

Remedy:

Review the section on configuring the A164UNIT table (Chapter 5:), and verify that the addresses of records <x> and <y>. Each unit address on a given port must be unique.

E307: UNIT rec <x>, configuration bad

Cause:

The BECO2200 DCA encountered non-fatal errors in record <x> of the A164UNIT table.

Effect:

Communication to this unit will be unavailable.

Restricted

A164-0CG-1.00-2

Full

33

 

Page 49
Image 49