Chapter 2: Configuring Win for the BECO2200 DCA

Chapter 2: Configuring Win for the BECO2200 DCA

This chapter describes how to configure the WESDAC Interface Node (WIN) for the BECO2200 DCA. The application number for WIN is B008. Refer to the WIN User’s Configuration Guide for more information on how to configure WIN. The functionality of all points required by the BECO2200 DCA is defined in the BECO2200 DCA Functional Specification.

2.1WESDAC Point Allocation

WESDAC data point allocation is accomplished by specifying the required number of points in the WIN configuration tables. Any points allocated to the BECO2200 DCA are maintained solely by the BECO2200 DCA. This means the BECO2200 DCA is the only application that may modify the value or the status of those points. All points allocated to the BECO2200 DCA are initialized to off-line and not communicating. If the WESDAC table is in NVRAM, points are initialized to the current value (state) in NVRAM. If the WESDAC table is in RAM, the points are initialized to zero (off).

 

WESDAC DATA TYPE

 

 

Number of points required

 

 

 

 

BECO 2200 M-0420

 

 

 

 

 

 

 

Binary Inputs

 

42

 

 

 

 

 

 

 

Binary Outputs

 

44+MDPC

 

 

 

 

 

 

 

Counters

 

38

 

 

 

 

 

 

 

Analog Input

 

281

 

 

 

 

 

 

 

Analog Outputs

 

78

 

 

 

 

 

 

 

Device Status

 

1

 

 

 

 

 

 

 

 

 

 

 

 

 

Table 2 Required Points BECO2200 Device

 

 

 

 

 

 