BECCO2200 DCA

GE Energy Services

Configuration Guide

F100: Bad A164APPL record counts, must be 1

Cause:

The A164APPL configuration table contained a number of records not equal to one.

Remedy:

Review the section on configuring the A164APPL table (Chapter 3:), and ensure that the table consists of only one record.

F101: Bad A164PORT record counts, must be > 0

Cause:

The A164PORT configuration table contained a number of records less than one.

Remedy:

Review the section on configuring the A164PORT (Chapter 4:), and ensure that the table consists of one or more records.

F102: Bad A164UNIT record counts, must be > 0

Cause:

The A164UNIT contained a number of records less than one.

Remedy:

Review the section on configuring the A164UNIT (Chapter 5:), and ensure that the table consists of one or more records.

F103: Bad CFG_DCA record counts, must be > 0

Cause:

The CFG_DCA configuration table contained a number of records less than one.

Remedy:

Review the section on configuring WIN for the BECO2200 DCA (Chapter 2:), and ensure that the table consists of one record for every DCA and DTA in the system.

Review the WIN User’s Configuration Guide for more information on how to configure WIN.

F104: Invalid DCA index

Cause:

The DCA Index configuration parameter in the A164APPL table specifies an invalid index into the WIN CFG_DCA table.

Remedy:

Review the section on configuring WIN for the BECO2200 DCA (Chapter 2:), and ensure that the table consists of one record for every DCA and DTA in the system.

Review the section on configuring the A164APPL table (Chapter 3:) and verify that the DCA Index parameter specifies a valid index into the WIN CFG_DCA table (the index is a zero based table offset).

A164-0CG-1.00-2Restricted

26

Full

 

Page 42
Image 42
GE BECCO2200 F100 Bad A164APPL record counts, must be, F101 Bad A164PORT record counts, must be, F104 Invalid DCA index