FVR-C9S-7UX

CAUTION:

The control circuit terminal wiring should be kept as far as possible from the main circuit wiring to prevent operational error due to noise interference. Never install them in the same duct or conduit. (A separation distance of 4 inches [10cm] or more is recom- mended.) If the control circuit wiring must cross the main circuit wiring, make sure it crosses at a right angle.

Use shielded, twisted wire for the control circuit wiring , which should be as short as possible (65 feet [20m] or less).

Install a surge absorber in parallel with any magnet contactors, solenoids, relays or timer coils, which are close to the drive.

Long wiring lengths between the motor and the drive will result in increased capacitance and leakage current. This may cause earlier activation of such protective functions as: overcurrent protection, overheating protec- tion and electronic thermal overload, or the error in current detection may become large. To avoid these, adjust the length of wiring between the drive and the motor so that is does not exceed the length shown below.

FVRF12C9S-7UX : 165 feet (50m)

FVRF25 to 002C9S-7UX : 325 feet (100m)

9. Application of Wiring and Equipment

Applicable motor output [Hp]

1/8

 

1/4

 

1/2

1

2

Drive type

 

FVRF12

 

FVRF25

 

FVRF50

FVRF001

FVRF002

 

 

C9S-7UX

C9S-7UX

C9S-7UX

C9S-7UX

C9S-7UX

Output rated capacity [kVA]

0.27

 

0.5

 

0.87

1.5

2.7

 

 

 

 

 

 

 

 

 

Applicable wire size

Main circuit

 

14

 

 

12

(AWG)

Contol circuit

 

 

 

 

24

 

 

MCCB

 

 

6

 

10

16

20

ELCB

 

 

6

 

10

16

20

Listed fuse*

 

 

20

 

 

30

* The use of quick-acting fuses is required to validate UL listing. The factory

C92-7-15

 

recommendation is Bussman type JKS or equivalent.

 

16

Page 16
Image 16