SERVICING

Alternately, the system CFM can be determined by operating the electric heaters and indoor blower WITHOUT having the compressor in operation. Measure the temperature rise as close to the blower inlet and outlet as possible.

If other than a 240V power supply is used, refer to the BTUH CAPACITY CORRECTION FACTOR chart below.

BTUH CAPACITY CORRECTION FACTOR

SUPPLY VOLTAGE

250 230 220 208

MULTIPLICATION FACTOR 1.08 .92 .84 .75

EXAMPLE: Five (5) heaters provide 24.0 KW at the rated 240V. Our actual measured voltage is 220V, and our measured temperature rise is 42°F. Find the actual CFM:

Answer: 24.0KW, 42°F Rise, 240 V = 1800 CFM from the TEMPERATURE RISE chart on the right.

Heating output at 220 V = 24.0KW x 3.413 x .84 = 68.8 MBH.

Actual CFM = 1800 x .84 Corr. Factor = 1400 CFM.

NOTE: The temperature rise table is for sea level installa- tions. The temperature rise at a particular KW and CFM will be greater at high altitudes, while the external static pressure at a particular CFM will be less.

TEMPERATURE RISE (F°) @ 240V

CFM

4.8

7.2

9.6

14.4

19.2

24.0

28.8

KW

KW

KW

KW

KW

KW

KW

 

 

 

 

 

 

 

 

 

600

25

38

51

-

-

-

-

700

22

33

43

-

-

-

-

800

19

29

38

57

-

-

-

900

17

26

34

51

-

-

-

1000

15

23

30

46

-

-

-

1100

14

21

27

41

55

-

-

1200

13

19

25

38

50

-

-

1300

12

18

23

35

46

-

-

1400

11

16

22

32

43

54

65

1500

10

15

20

30

40

50

60

1600

9

14

19

28

38

47

57

1700

9

14

18

27

36

44

53

1800

8

13

17

25

34

42

50

1900

8

12

16

24

32

40

48

2000

8

12

15

23

30

38

45

2100

7

11

14

22

29

36

43

2200

7

11

14

21

27

34

41

2300

7

10

13

20

26

33

39

ELECTRIC HEATER CAPACITY BTUH

HTR

3.0

4.7

6.0

7.0

9.5

14.2

19.5

21.0

KW

KW

KW

KW

KW

KW

KW

KW

KW

BTUH

10200

16200

20400

23800

32400

48600

66500

71600

 

 

 

 

 

 

 

 

 

FORMULAS:

Heating Output = KW x 3413 x Corr. Factor

Actual CFM = CFM (from table) x Corr. Factor

BTUH = KW x 3413

BTUH = CFM x 1.08 x Temperature Rise (T)

CFM = KW x 3413 1.08 x T

T = BTUH

CFM x 1.08

S-61A CHECKING HEATER LIMIT CONTROL(S)

Each individual heater element is protected with a limit control device connected in series with each element to prevent overheating of components in case of low airflow. This limit control will open its circuit at approximately 150°F.

HIGH VOLTAGE!

Disconnect ALL power before servicing or installing. Multiple power sources may be present. Failure to do so may cause property damage, personal injury or death.

1.Remove the wiring from the control terminals.

2.Using an ohmmeter, test for continuity across the nor- mally closed contacts. No reading indicates the control is open - replace if necessary.

IF FOUND OPEN - REPLACE - DO NOT WIRE AROUND.

S-61B CHECKING HEATER FUSE LINK (OPTIONAL ELECTRIC HEATERS)

Each individual heater element is protected with a one time fuse link which is connected in series with the element. The fuse link will open at approximately 333°.

WARNING

Disconnect ALL power before servicing.

1.Remove heater element assembly so as to expose fuse link.

59

Page 59
Image 59
Goodmans ASX, GSZ 61A Checking Heater Limit Controls, 61B Checking Heater Fuse Link Optional Electric Heaters, Formulas