13 Finishing

13 Finishing

A. Mantel and Wall Projections

WARNING! Risk of Fire! Comply with all minimum clear- ances as specified. Framing closer than the minimums list- ed must be constructed entirely of noncombustible materials (i.e., steel studs, concrete board, etc.)

The CMOD door will overlap the appliance. See Figure 13.3 and 13.4.

Combustible Mantels

Note: All

 

TO CEILING

measurements

 

18

 

in inches.

 

 

 

 

 

 

 

12

 

 

 

11

 

 

 

10

32

 

 

9

 

 

 

 

8

25

 

 

7

19

 

 

6

 

 

18

 

 

5

 

 

17

 

 

4

16

 

 

3

 

 

15

 

 

 

 

 

 

14

 

 

 

13

 

2-1/2

12

 

 

11

 

 

 

 

 

 

10

 

 

 

5

 

 

 

MEASUREMENTS FROM

 

 

TOP EDGE OF THE OPENING

 

Note: Measurement is taken from top of the opening, NOT the top of the fireplace.

Figure 13.1 Minimum Vertical and Maximum Horizontal

Dimensions of Combustibles

Combustible Mantel Legs or Wall Projections

INTERIOR WALL

TOP VIEW

A

B

 

FIREPLACE OPENING

 

MANTEL LEG OR WALL PROJECTIONS

If A minimum is ____, then B maximum is_____.

A

Inches

2-7/16

3-7/16

4-7/16

5-7/16

6-7/16

7-7/16

Millimeters

62

87

113

138

164

189

 

B

Inches

1

2

3

4

5

Millimeters

25

51

76

102

127

Figure 13.2 Combustible Mantel Leg or Wall Projections (Acceptable on both sides of opening)

Figure 13.3 Appliance Surround

3/8 IN.

1-3/4 IN.

3/8 IN.

Figure 13.4 Door Overlaps Surround

Heat & Glo • 6000CMOD-IPI, 8000CMOD-IPI2241-900 Rev. H • 5/12