A. Chimney Requirements

A. Chimney Requirements

Vertical distances are measured from the base of the fire- place as shown in Figure 5.2.

Minimum overall straight height

14

(4.27 m)

Minimum height with offset/return

16.5 ft

(5.03 m)

• Maximum height

90 ft

(27.43 m)

• Maximum chimney length between an offset

20 ft

(6.1 m)

 

and return

 

 

• Maximum distance between chimney

35 ft

(10.67 m)

 

stabilizers

 

 

Double offset/return minimum height

20 ft

(6.1 m)

• Maximum unsupported chimney length

6 ft

(1.83 m)

 

between the offset and return

 

 

• Maximum unsupported chimney height above

35 ft

(10.67 m)

 

the fireplace

 

 

• Maximum unsupported chimney above roof

6 ft

(1.83 m)

To determine the chimney components needed to complete your particular installation, follow the steps below:

Determine the total vertical height of the fireplace installation. This dimension is measured from the base of the fireplace assembly to the point where the smoke exits the termination cap.

Subtract the effective height of the fireplace assembly from the overall height of the fireplace installation (measured from the base of the fireplace to the bottom of the termination cap).

Refer to Table 5.1 to determine what components must be selected to complete the fireplace installation.

Determine the number of ceiling firestops, stabilizers, roof flashing, etc. required to complete the fireplace installation.

Note: A maximum of two pairs of offsets and returns may be used.

Offsets/Returns WARNING

Fire Risk

Must maintain 2 in. (51 mm) air clearance to insulation and other combustible materials.

Table 5.1

HEIGHT OF CHIMNEY COMPONENTS

in.

mm

Chimney Stabilizer

 

 

 

SL11

4-3/4

121

Ceiling Firestops

 

 

 

FS538

0

0

 

FS540

0

0

6 ft (1.8 m) max. unsupported run

20 ft (6.10 m) max. pipe between an offset & return

Ceiling Firestop

44in.

(1118 mm) Effective Height

6 ft (1.83 m) max. unsupported chimney above roof

35 ft (10.7 m) max. straight unsupported chimney height

13.25ft (4.04 m) min. height/single offset-return 20 ft. (6.10 m) min. height/double offset-return

90 ft (27.4 m) max. height

Offsets/Returns

 

 

 

SL1130

18

457

Roof Flashing

 

 

 

RF570

0

0

 

RF571

0

0

Chimney Sections*

 

 

 

SL1106

4-3/4

121

 

SL1112

10-3/4

273

 

 

 

 

 

SL1118

16-3/4

425

 

 

 

 

 

SL1136

34-3/4

883

 

SL1148

46-3/4

1187

* Dimensions reflect effective height.

 

 

Figure 5.2 Chimney Requirements

Roof Flashing CAUTION

Do NOT connect this fireplace to a chimney flue servicing another appliance.

Do NOT connect to any air distribution duct or system.

Heat & Glo • Multi-Sided Woodburning Fireplace • 34977 Rev T • 11/07