6 Complete the Enclosure
A. Chimney Termination
Chimney Termination Requirements (See Figures 6.1 and 6.2)
•Must have a cap approved and listed for this fireplace system
•Must not be located where it will become plugged by snow or other material
•Must terminate at least 3 ft (914 mm) above the roof and at least 2 ft (610 mm) above any portion of the roof within 10 ft (3.05 m)
•Must be located away from trees or other structures
Slanted Roofs
Chimney must extend 3 ft (.9 m) above the roof
Chimney must extend 2 ft (.6 m) above any portion of the roof within 10 ft (3 m) of the chimney
Flat Roofs
Chimney must extend 3 ft (.9 m) above the roof
Chimney must extend 2 ft (.6 m) above any portion of the roof within 10 ft (3 m) of the chimney
Figure 6.1 Termination Requirements
Gas, Wood or Fuel | Termination Caps Same Height | |
Oil Termination | ||
|
|
| 8 ft |
| Gas, Wood or Fuel |
|
| A | (2.44 m) |
| Oil Termination |
|
18 in. | (min. for |
|
| ||
|
|
|
| ||
| 20 in. |
|
| 8 ft | |
(457 mm) |
| (508 mm) |
|
| |
|
|
|
| (2.44 m) | |
|
| (min. for direct vent) |
|
| |
B |
|
|
| (min. for | |
| to |
|
| ||
| Wood | 20 in. min. * | 20 in. | ||
|
| Perpendicular | |||
|
| Wall |
| (508 mm) | (508 mm) |
|
|
| (min. for direct vent) | ||
Gas |
|
|
|
| to |
Termination |
|
|
|
| Perpendicular |
|
|
|
|
| Wall |
|
|
|
| Termination Caps Staggered Height |
|
| * If using decorative cap cover(s), this distance may | |
|
|
|
|
|
|
|
| |
|
| A |
| Gas Termination | Wood or Fuel Oil Termination |
|
| need to be increased. Refer to the installation instruc- |
|
| B |
| 6 in. (152 mm) min. | 20 in. (508 mm) min. |
|
| tions supplied with the decorative cap cover. |
|
|
|
|
|
| |||
Figure 6.2 | Multiple Chimneys |
|
|
|
|
22 | Heat & Glo • |