7 Vent Information and Diagrams

7 Vent Information and Diagrams

A. Vent Guidelines

WARNING! Risk of Fire and Asphyxiation! This appliance requires the specified pipe for operation. Incorrect pipe may cause spillage, condensation and overheating.

These models require the following size B-vent double wall, or single wall rigid or flex vent pipe.

Models

Pipe Size

SL-550TV-IPI-E

5 inch

SL-750TV-IPI-E

5 inch

SL-950TV-IPI-E

6 inch

Follow pipe manufacturer’s installation guidelines when installing the appliance.

WARNING! Risk of Fire, Explosion or Asphyxiation! DO NOT connect this gas appliance to a chimney flue serving a separate solid-fuel or gas burning appliance.

Vent this appliance directly outside.

Use separate vent system for this appliance.

May impair safe operation of this appliance or other appli- ances connected to the flue.

B. Vent System Configuration

CAUTION! Risk of Fire! ALL vent configuration speci- fications MUST be followed. This product is tested and listed to these specifications. Appliance performance will suffer if specifications are not followed.

Rise to Run Ratio = 2:1

Maximum Total Horizontal Run = 15 Feet Minimum Total Vertical Rise = 9 Feet Maximum Total Vertical Rise = 48 Feet Maximum Number of Elbows: Two 90º or Four 45º

WARNING! Risk of Fire or Explosion! Insulation and other combustibles must not infringe on clearances.

ALWAYS maintain specified clearances around venting and firestop systems.

Install firestops as specified.

Failure to keep insulation or other material away from vent pipe may cause fire.

 

MINIMUM CLEARANCES

 

ARE PER VENT

 

MANUFACTURER’S

 

SPECIFICATIONS

 

METAL

9 FEET

PLUMBER’S

STRAP

MINIMUM

 

48 FEET

MAXIMUM

VENT SUPPORTS ARE PER

VENT MANUFACTURER’S

SPECIFICATIONS

Figure 7.1

Note: Horizontal runs require

 

1/4 in. rise per foot run.

 

VENT SUPPORTS

 

ARE PER VENT

METAL

MANUFACTURER'S

SPECIFICATIONS.

PLUMBERS' STRAP

MAXIMUM HORIZONTAL RUN IS 50%

OF VERTICAL. HORIZONTAL RUN

CANNOT BE MORE THAN 15 FT.

Figure 7.2

 

 

MAXIMUM

 

HORIZONTAL

 

15 FEET

MINIMUM VERTICAL 9 FEET

45DEGREES ELBOW

90DEGREES ELBOW

Figure 7.3

OFFSETS EXCEEDING 45 DEGREES ADAPT HORIZONTAL LIMITATIONS

Note: Maximum horizontal distance is 50% vertical vent height.

Heat & Glo • SL-550 / 750 / 950TV-IPI-E2119-900 Rev. J • 12/09

23