D. Mantel and Wall Projections

WARNING! Risk of Fire! Comply with all minimum clear- ances to combustibles as specified. Framing or finishing material closer than the minimums listed must be construct- ed entirely of noncombustible materials (i.e., steel studs, concrete board, etc).

Combustible Mantels

1/2 in. Thick Wall

Sheathing 12 in. MAX.

14 in. MEASUREMENT FROM TOP OF MIN. FIREPLACE OPENING

Figure 5.3 Clearances To Combustible Mantels Or Other Combustibles Above Appliance

Non-combustible Mantels

1/2 in. Thick Wall

Sheathing 12 in. MAX.

14 in. MEASUREMENT MIN. FROM TOP OF FIREPLACE

OPENING

Figure 5.4 Clearances To Non-Combustible Mantels Or Other Non-Combustibles Above Appliance

Note: For non-combustible fireplace finish mate- rial (marble, stone, etc) specifications refer to Figure 13.13 and Figure 13.15.

Combustible Mantel Legs Or Wall Projections Extending Past The Face Of The Fireplace

2 IN.

MINIMUM 3 FT. MAXIMUM

6 IN.

MINIMUM

Figure 5.5 Combustible Mantel Leg or Wall Projections (Acceptable on both sides of opening)

Non-combustible Mantel Legs Or Wall Projections Extending Past The Face Of The Fireplace

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3 IN.

 

 

 

 

 

 

 

 

 

UNLIMITED

MINIMUM

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Figure 5.6 Non-Combustible Mantel Leg or Wall Projections

Î

(Acceptable on both sides of opening)

 

Front Side Finishing Detail

 

1.00 in.

 

FRAMING

 

1-9/16 in.

 

1/2 in. BUILDING MATERIAL

Figure 5.7

Front Side Finishing Detail

18

Heat & Glo • SLR • 2143-900 Rev. B • 7/08

Page 18
Image 18
Heat & Glo LifeStyle SLR (COSMO) owner manual Mantel and Wall Projections, Combustible Mantels, Non-combustible Mantels