Heat & Glo LifeStyle SLR (COSMO) Top Vent - Horizontal Termination - continued, H2 V2, V1 Minimum

Models: SLR (COSMO)

1 67
Download 67 pages 20.51 Kb
Page 25
Image 25
Top Vent - Horizontal Termination

1. Top Vent - Horizontal Termination - (continued)

 

 

 

 

 

 

Top Vent - Horizontal Termination

 

 

 

 

 

 

 

Venting with 3 elbows

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SLR

 

 

 

V1 Minimum

H1 + H2 Maximum

V2

V1 + V2 Minimum

 

90° Elbow

6 ft.

 

 

 

1.8 m

*

*

 

1 ft.

305 mm

10 ft.

 

 

 

3.0 m

*

*

 

2 ft.

610 mm

12 ft.

 

 

 

3.7 m

*

*

 

3 ft.

914 mm

14 ft.

 

 

 

4.3 m

*

*

 

 

 

H1

+ H2

MAX. =14 ft. (4.3 m)

 

 

 

 

V1 + V2 + H1

+ H2 MAX. = 40 ft. (12.2 m)

 

 

*No specific restrictions on this value EXCEPT V1 + V2 + H cannot exceed 40 ft. (12.2 m)

 

Note: Use SLP Series components only.

Note: There MUST be a 25% reduction in total H when using flex vent except when using the simple up and out installation (see Figure 7.3).

Note: The SLP-HRC-SS and SLP-HRC-ZC-SS termination caps are not approved for use with propane (LP) fuel.

H2

V2

H1V1

Figure 7.6

Heat & Glo • SLR • 2143-900 Rev. B • 7/08

25