Heat Controller B-MMH09FA-1, B-MMH12FA-1, B-MMC12FA-1, B-MMC09FA-1, A-MMH24FA-1, A-MMH36FA-1 manual

Models: A-MMC24FA-1 B-MMH12FA-1 A-MMC18FA-1 B-MMC12FA-1 A-MMH36FA-1 A-MMH18FA-1 B-MMH09FA-1 A-MMC36FA-1 A-MMH24FA-1 B-MMC09FA-1

1 84
Download 84 pages 8.66 Kb
Page 23
Image 23

Flaring Work and Connection of Piping

Flaring Work and Connection of Piping

Flaringwork

The main cause for gas leakage is due to defects in flaring work. Carry out correct flaring work using the following procedures.

Cut the pipes

1.Use the copper pipe purchased locally.

2.Measure the distance between the indoor and the outdoor unit.

3.Cut the pipes a little longer than measured distance.

4.Cut the cable 1.5m (5.0ft) longer than the pipe length.

Burrs removal

1.Completely remove all burrs from the cut cross section of pipe/tube.

2.Put the end of the copper tube/pipe in a downward direction as you remove burrs in order to avoid dropping burrs into the tubing.

Adding the Flare Nut

Remove flare nuts attached to the indoor and outdoor unit, then put them on the end of the copper pipe once you hav completed burr removal (it is not possible to put them on after the flaring work)

Flaring work

Carry out flaring work using flaring tool as shown below.

Firmly hold copper pipe in the proper size hole dimension of the bar as shown in the table below.

Copper

 

Slanted

Uneven Rough

pipe

90°

 

 

Pipe

 

 

 

Reamer

Point down

Flare nut

Copper tube

Outside diameter

A

 

 

 

mm

inch

mm

Ø6.35

1/4

0~0.5

Ø9.52

3/8

0~0.5

 

"A"

 

Handle

Bar

Bar

 

 

Yoke

 

 

 

 

 

 

Cone

 

Copper pipe

 

 

 

Clamp handle

Red arrow mark

 

 

 

- 23 -

Service Manual

Page 23
Image 23
Heat Controller B-MMH09FA-1, B-MMH12FA-1, B-MMC12FA-1, B-MMC09FA-1, A-MMH24FA-1, A-MMH36FA-1, A-MMH18FA-1, A-MMC24FA-1 manual