Charging

Charging

Each outdoor unit is factory charged (see rating plate) for the evaporator as well as a 7.5m(25ft) line set for each indoor line. Any time the total line set is used either shorter or longer then the nominal line set length the refrigerant charge has to be adjusted.

Whether the line set is made shorter or longer you must adjust the charge based on how many m(ft) of tubing are either added or removed based on 20g(0.22oz) of R-410A per meter(foot).

 

Max total length

Max length of

Min length of

Max Elevation

Max elevation

Additional

 

between each indoor

Capacity (Btu/h)

of all pipes

between indoor

each pipe (A/B)

each pipe (A/B)

unit and outdoor unit

Refrigerant

 

(A+B)

 

 

(h1)

units (h2)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

18k

30m(100ft)

15m(50ft)

3m(10ft)

7.5m(25ft)

7.5m(25ft)

20g/m(0.22oz/ft)

 

 

 

 

 

 

 

24k

30m(100ft)

15m(50ft)

3m(10ft)

7.5m(25ft)

7.5m(25ft)

20g/m(0.22oz/ft)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Max total length

Max length of

Min length of

Max Elevation

Max elevation

Additional

 

between each indoor

Capacity (Btu/h)

of all pipes

each pipe

each pipe

between indoor

unit and outdoor unit

Refrigerant

 

(A+B+C)

(A/B/C)

(A/B/C)

(h1)

units (h2)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

36k

45m(150ft)

15m(50ft)

3m(10ft)

7.5m(25ft)

7.5m(25ft)

20g/m(0.22oz/ft)

 

 

 

 

 

 

 

Example: A 80ft line set is used for tri-zone, an additional 5 ft X 0.22 ounces per foot= add 1.1 ounces of R-410A

Important:

If you are ever uncertain of the unit charge, reclaim, evacuate and weigh in the correct charge using the charge amount speci- fied on the unit's rating plate, adjusting for line sets longer or shorter than 7.5m(25ft) for each indoor unit. Unit is critically charged.