Flaring Work and Connection of Piping

Check

1.Compare the flare work like the figure on the right.

2.If a flared section is defective, cut it off and repeat the flar- ing process again.

Smooth all around

Inside is shiny without scratches

= Improper flaring =

Inclined Surface Cracked Uneven

damaged thickness

Even length

all around

Connecting the Piping

Indoor

1. Prepare the indoor unit's piping and drain hose for installation through the wall.

2. Remove the plastic tubing retainer(see illustration on the right) and pull the tubing and drain hose away from chassis.

For right rear piping

1.Route the indoor tubing and the drain hose in the direction of rear right.

2.Insert the connecting cable into the indoor unit from the out- door unit through the piping hole.

Do not connect the cable to the indoor unit.

Make a small loop with the cable for easy connection later.

3.Tape the tubing, drain hose, and the connecting cable. Be sure that the drain hose is located on the lowest side of the bundle. Locating on the Upper side can cause the conden- sation to overflow in the drain pan inside the indoor unit.

If the drain hose is routed inside the room, insulate the hose with an insulation material* so that dripping from "sweat- ing"(condensation) will not damage furniture or floors. *Foamed polyethylene or equivalent is recommended.

Drain hose

Tape

Connecting pipe

Drain hose

Connecting cable

Wall Mounted Multi-Zone Split System Air Conditioner

- 24 -

Page 24
Image 24