Operation

FunctionofOutdoor Unit

Outdoor Unit

Operating Step

Compressor step varies considering conditions such as room temperature, operating room number, temperature gap between room temperature and set point temperature and so on.

LEV Control

The linear expansion valve is pulse is modulated to keep constant superheat or subcooling.

Outdoor Fan Control

Outdoor fan operates at High or Off to respond to the load condition.

R/Valve Control(Heating Model Only)

Reversing valves is used to change cooling to heating, heating to cooling.

Defrost Function

After 45 minutes in heating mode, defrost mode will take effect if the outdoor pipe temp is below 5°C (23°F). The defrost mode will end when the outdoor pipe temp is above 12°C (53.6°F) or after the unit has been operated in cooling mode for 9 minutes.

To de-ice the outdoor heat exchanger in low temperature conditions, the unit will defrost by changing the operating mode from heating to cooling, while turning off both indoor and outdoor fans.

Oil Return System

In single(one) compressor operation duration, another compressor will operate for 30 seconds every 1 hours.

compressor Overload Protection

To protect compressor from being overloaded, the compressor overload protector will turn the compressor off.

High Pressure Protction

If the refrigerant cycle's pressure is too high, above 36.7 kgf/cm2 (521.997psi), the high pressure switch will turn the compressor off.